Table l-dimensions in inches, Figure 4—thermostat connections, Table ll-ratings and performance – Carrier 58DE User Manual
Page 2: 0 - 0 —r
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
m
Figure 2—Dimensional Drawing
TABLE l-DIMENSIONS IN INCHES
SIZE 58DE
A
D
E
VENT SIZE
SHIP WT
050-200
14 Vs
] 2 %
12 У
4
131
080-100
1714
Ì
5
V
4
16
4
138
080-200
1 7
У
2
] 5 %
16
4
143
100-100
] 7 %
1 5
У
4
16
5
165
100-200
I
7
V
2
15У
16
5
170
125-100
21
I
9
V
4
19У,е
5
207
125-200
21
1 9
У
4
19Уе
5
212
150-200
2 4 % ,
2 2
У
4
23
6
240
Make field low-voltage connections at the low-voltage ter
minal strip on units equipped with a cooling relay. On heat
ing-only units, two flagged wires are provided for making
the thermostat connections. See Figure 4.
Set the thermostat heat anticipator at
0.9.
If additional con
trols are connected in the thermostat circuit, their amp
draw must he added to this setting. Failure to make the set
ting will result in improper operation of the thermostat.
The room thermostat should be located where it will be in
the natural circulating path of room air. Avoid locations
where the thermostat would be exposed to cold air infiltra
tion, drafts from windows, doors, or other openings leading
to the outside, or exposure to air currents from warm or cold
air registers; or to exposure where the natural circulation of
the air is cut off—such as behind doors, above or below man
tels, shelves, etc.
The thermostat should not be exposed to heat from nearby
fireplaces, radios, televisions, lamps, or rays from the sun.
Nor should the thermostat be mounted on a wall containing
pipes or warm air ducts, or a flue or vent that could affect its
operation and prevent it from properly controlling the room
temperature. Any hole in the plaster or panel through which
Q (p (p
FIELD LOW-VOLTAGE WIRING — •
FIELD
HIGH-VOLTAGE
WIRING-
FACTORY LOW-VOLTAGE WIRING-
0.-----------
0--
0-
0--
1—r
Ш
FURNACE ___________
LOW-VOLTAGE
TERMINAL BOARD
m
o-||-o|------- 1 I
_____ I J
9
.—
POWER SUPPLY
SEE UNIT
roxmrMCMr
rating
PLATE
for
voltage
.
CONTROL BOX
HERTZ,
& PHASE
Figure 3—Heating and Cooling Application
Wiring Diagram
NOTE: If any of the original wire, as supplied, must be replaced,
use same type or equivalent wire
#
UNITS WITH COOLING RELAY HEATING ONLY UNITS
Figure 4—Thermostat Connections
TABLE ll-RATINGS AND PERFORMANCE*
SIZE 58DE
NATURAL AND LP
TEMP RISE
HEATING
COOLING
Input Btuh
Output Btuh
RANGE
Ext Static Pressure
CFM
Ext Static Pressure
CFM
050-200
50,000
40,000
45- 75
-
617
0.5
800
080-100
080-200
80,000
64,000
70-100
45-100
0 . 1 2
700
855
0 . 5
1200
100-100
100-200
100,000
80,000
70-100
45-100
0.15
870
910
0 . 5
1400
125-100
125-200
125,000
100,000
70-100
45-100
0.20
1100
1206
0 . 5
1600
150-200
150,000
120,000
45- 75
0.20
1736
0 . 5
1920
t
*The above ratings are approved for altitudes to 2000 ft For elevations above 2000 ft, reduce ratings 4% for each 1000 ft above sea level