beautypg.com

Sequence of operation, 58drc counterflow gas-fired furnaces – Carrier 58DRC User Manual

Page 4

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

HEATING A COOUHG

58DRC

Counterflow Gas-Fired Furnaces

Fig. 8 — Amp Draw Check with Ammeter

The room thermostat should be located where it will

be in the natural circulation path of room air. Avoid loca­

tions where the thermostat would be exposed to cold-air
infiltration, drafts from windows, doors, or other open­

ings leading to the outside, or exposure to air currents

from warm- or cold-air registers; or to exposure where

the natural circulation of the air iS- cut off — such as
behind doors, above or below mantels, shelves, etc

The thermostat should not be exposed to heat from

nearby fireplaces, radios, televisions, lamps, or rays from
the sun. Nor should the thermostat be mounted on a wall
containing pipes or warm-air ducts, or a flue or vent that

could affect its operation and prevent it from properly

controlling the room temperature. Any hole in the plaster

or panel through which the wires pass from the thermo­
stat should be adequately sealed with suitable material to
prevent drafts from affecting the thermostat

PRlNTED-ClRCUlT CONTROL CENTER — Each

furnace features a printed-circuit control center. This will
aid the installer and service technician when installing and
servicing the unit. See Fig. 9. A low-voltage terminal

board is marked for easy connection of field wiring.

4 и

^ Н

Fig. 9 — Printed-Circuit Control Center

Sequence of Operation

NOTE; The wiring diagram shown in Fig. 10 is for
heating/cooling units.

HEATING — Gas and electrical supplies must be turned

on at the furnace.

NOTE; When power is applied to heat relay coil 2 A in the

control circuit, the normally closed contacts in the blower
circuit will open.

BDP 646 Gas Valve (HD Models) — When the thermo­

stat calls for heat, the control circuit is closed between
terminals R and W. Power from transformer 1A through
fusible link 11C and limit switches 7H1 / 7H2 energizes the
pilot valve portion of automatic gas valve 5F and pilot
igniter 6F. The pilot valve opens, permitting gas flow to
the pilot burner where it is ignited.

The pilot valve portion of automatic gas valve 5F is a

solenoid consisting of a PICK and a HOLD coil. Both

the PICK and the HOLD coils must be energized to open

the valve, but only the HOLD coil must be energized to
keep it open

1A

2A

2F

3D
4A

5F

6C1
6F
6H

Transformer 115/24

Relay-Heat (SPST-
N C )

Relay-Cool (DPDT)
Blower Motor
Run Capacitor

Gas Valve (2-Circuit)

Printed-Circuit Board

Piiot Igniter

Safety Pilot (Flame
Sensing)

7H1

— Limit Switch (SPST-

N C )

7H2

— Auxiliary Limit Switch

(SPST-N C ) Manual

Reset

Summer/Winter

Switch (if equipped)

Blower Door Switch
(SPST-N O )
Fusible Link

9A

9G —

11C

Fig. 10 — Line-to-Line Wiring Diagram for

Sizes 045-095 IID Natural Gas

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations

Book|1 14

PC101

Catalog No 535-843

Printed in U S A

Form 58DRC-1 SI

Pg4

7-85

Replaces:New

ronlanorvionf Home iica

Cna^iticw4 Dat-fc