beautypg.com

Mtek6000 series user's manual, Description jumper position – Compaq MTEK6000 User Manual

Page 69

background image

MTEK6000 SERIES USER'S MANUAL

January 2002 D-3

JP6 selects a power source for external analog transducers at TB3-1 & TB6-1 as follows:

Description Jumper

position

use on board +12V dc supply ( 20 mA max )

JP6 = A

use on-board +5V dc supply ( 20 mA max)

JP6 = B

Vin external supply (from Metretek UPS)

JP6 = C


External Analog #2: Use Terminal 35 (transducer power)

Terminal 36 (transducer output)

Terminal 37 (transducer common)

For a 4-to-20 mA type transducer put JP7 and JP8 in.

For a 1-to-5 volt type transducer take JP7 and JP8 out.


External Analog #1: Use

Terminal 20 (transducer power)

Terminal 21 (transducer output)

Terminal 22 (transducer common)

For a 4-to-20 mA type transducer put JP9 and JP10 in.

For a 1-to-5 volt type transducer take JP9 and JP10 out.


Pulse Input #1:

Use

Terminal 32 (set input)

Terminal 33 (ground)

Terminal 34 (reset input)


Pulse Input #2:

Use

Terminal 29 (set input)

Terminal 30 (ground)

Terminal 31 (reset input)


Status / Pulse Input #3: Use Terminal 26 (set input)

Terminal 27 (ground)

Terminal 28 (reset input)


External Access to the Mechanical Index: Terminal

25 (normally open)

(separate form C contacts)

Terminal

24 (common)

Terminal 23 (normally closed)