MTEK6000 SERIES USER'S MANUAL

D-2

January 2002

61-OPT Revision A – Option Board

Pulse Output 1: Use

Terminal 19 (normally open contact)

Terminal 18 (common 1)

and

Terminal 17 (normally closed contact)

For form A output: put JP1 and JP1A both in position A to B.

For form C output: put JP1 and JP1A both in position B to C (requires external wetting).


Pulse Output 2: Use

Terminal 16 (normally open contact)

Terminal 15 (common 2)

and

Terminal

14 (normally closed contact)

For form A output: put JP2 and JP2A both in position A to B.

For form C output: put JP2 and JP2A both in position B to C (requires external wetting).


Pulse Output 3 : Use

Terminal 13 (normally open contact)

(optional)

Terminal

12 (common 3)

and

Terminal

11 (normally closed contact)

For form A output: put JP3 and JP3A both in position A to B.

For form C output: put JP3 and JP3A both in position B to C (requires external wetting).


Pulse Output 4: Use

Terminal 10 (normally open contact)

(optional)

Terminal

9 (common 4)

and

Terminal

8 (normally closed contact)

For form A output: put JP4 and JP4A both in position A to B

For form C output: put JP4 and JP4A both in position B to C (requires external wetting).


JP5 can be used as a convenient means to connect pulse input 2 as follows:

Description Jumper

position

connect pulse input 2 to mechanical
index secondary output

JP5 A, B, & C all in

otherwise

JP 5 A, B, & C all out (default)