• To enlarge batteries life expectancy it is recommendable to fully discharge
UPS one every 2 to 3 months
• During UPS storage recharge batteries according to the following table:
WARNING: BATTERIES MAINTENANCE
• Batteries capacity, in general (of all kinds), decrease with time and use.
• Our products contain high quality batteries only.
• Batteries useful life in our UPS is between 4 and 5 years, considering environment temperature under 25 ºC and optimal
operational conditions. This time can be dramatically reduced by high temperature and other adverse operation condition.
• Batteries life expectancy may be also affected by other operation conditions such as electrical service quality as well as
number and kind of equipments connected to UPS
• Batteries should be periodically tested to check capacity and assure and appropriate back up.
Storage Temperature
Recharging Frequency
Recharging Time
-25°C a +30°C
Every 4 months
During 6 hours
+30°C a +45°C
Every 2 months
During 6 hours
SAFETY STANDARDS
SAFETY:
IEC/EN 62040-1
EMI (Radiated):
IEC/EN 62040-2 (Cat 3)
EMI (Conducted):
IEC/EN 62040-2 (Cat 3)
EMS Power-Frequency Magnetic Field:
IEC/EN 61000-4-8 (Level 4)
EMS Low Freq. Signals:
IEC/EN 61000-2-2
EMS (ESD):
IEC/EN 61000-4-2 (Level 4)
EMS (RS):
IEC/EN 61000-4-3 (Level 3)
EMS (EFT):
IEC/EN 61000-4-4 (Level 4)
EMS (SURGE):
IEC/EN 61000-4-5 (Level 4)
EMS (CS):
IEC/EN 61000-4-6 (Level 3)
This product has been designed to operate in industrial and commercial applications. If it is used in different application some considerations for
avoiding interferences could be necessary.