SETTING / OTHERS
Others:
-->
Hot Standby
Backup Time
Hot Standby:
-->
Status: Disable
Backup Time:
-->
Batt Groups: 1
Batt Cap: 9AH
Factor: 1.0
HOT STANDBY:
ENABLE: It allows UPS to restart after a long AC failure even UPS has
no batteries connected.
DISABLE: It allows UPS to work as standard UPS. It will only restart
when AC recovery is detected if UPS has batteries connected.
BACKUP TIME PARAMETERS:
BATT GROUPS: Set the quantity of battery groups connected from 1 to
6. Default is 1.
BATT CAP: Set the battery capacity in AH. Default is 9AH.
FACTOR: This factor is used to calculate remaining backup time
displayed on LCD. Default is 1.
F5. ALARMS & ERROR SCREEN
Alarm Info
Fault:
14: Output Short
Warning:
01: Batt Open
In this screen warnings and faults are recorded.
Warning and error messages are described in following tables.