- ONLINE 6K/10K RACK-TOWER ISOTX UPS

ENGLISH

__________________________________________________________________________________________________________________________

www.xmart-ups.com

130717 RT9- 6K-10K (ENG)

- 37

SETTING / BATTERY

Battery:

-->

DisChg Protect: Enable

990 min.

Batt Test Type:

Till Batt Low

Battery:

-->

DisChg Protect: Enable

990 min.

Batt Test Type:

Short Time:

10 sec

Battery:

-->

DisChg Protect: Enable

990 min.

Batt Test Type:

Long Time:

10 min

DISCHARGE PROTECTION FUNCTION:


Enable:
UPS will shutdown automatically to protect batteries.

Shutdown will be produced according to time in minutes set below
(from 000 to 990 min.)

Disable: Batteries protection disable. UPS will run until reach very low
battery level.

000-990: Set time in minutes for Discharge protection function.

BATTERY TEST TYPE:

Short Time: Battery tests will be performed during 10 seconds.


Long Time:
Battery tests will be performed during 10 minutes.

Till Battery Low: Battery tests will be performed until reaching battery
low level.


SETTING / CALIBRATION

Calibration:

-->

Batt: 273.0 +0.0

Inv: 220.0 +0.0

Chg: 273.0 +0.0


BATT: Calibrate value indicated in LCD for battery voltage.


INV: Adjust the inverter output voltage. Available only in:

Online mode
Battery mode
CVCF mode

CHG: Adjust the charger output voltage. Available only in:

Bypass mode
Online mode
ECO mode
CVCF mode
** Batteries must be disconnected from charger before making any
adjustment.