SETTING / ECO
ECO:
-->
Status: Disable
High Loss: 232V
Low Loss: 184V
High Loss: 52Hz
Low Loss: 48Hz
STATUS ENABLE: ECO function enable
STATUS DISABLE: ECO function disable
HIGH LOSS V: Acceptable high limit for input voltage for UPS in ECO
mode.
LOWLOSS V: Acceptable min. limit for input voltage for UPS in ECO
mode.
HIGH LOSS F: Acceptable high limit for input frequency for UPS in
ECO mode.
LOWLOSS F: Acceptable min. limit for input frequency for UPS in ECO
mode.
SETTING / OUTPUT
Output:
-->
Volt: 220.0V
Freq: Auto
CVCF: Disable
VOLT:
208: set output voltage to 208Vac
220: set output voltage to 2220Vac
230: set output voltage to 230Vac
240: set output voltage to 240Vac
FREQ:
50Hz: Set output to 50Hz
60Hz: Set output to 60Hz
ATO: Set output according to input frequency.
From 46-54Hz set to 50Hz. From 56 to 64Hz set to 60Hz.
CVCF: Set if frequency conversion is activated.
Enable: Output frequency is fixed in 50Hz or 60Hz according to
previous FREQ setting
Disable: Converter function disables. Output frequency will be
synchronized with input frequency.