beautypg.com

Winco ULPSS21/E WITH DSE 7310 ENGINE CONTROL User Manual

Page 6

background image

Page 4

3025-00

60706-240

**** CAUTION ****

EQUIPMENT DAMAGE - These units must be mounted on a solid

concrete pad to prevent air from exiting under the unit. Allowing

air to exit under the unit may cause the unit to overheat from lack

of proper air flow.

Before beginning the installation process recheck the rating of the

generator set and its transfer switch rating. Be certain they can

handle the intended load and are compatible with the entrance

voltage, phase and current ratings. Plans for installation should

be prepared with proper attention to mechanical and electrical en-

gineering detail to assure a satisfactory system installation. The

information in this manual is offered only as a guide to finalizing

your installation plans. For full service switching the A.T.S. must

have a fusible disconnect (circuit breaker) installed before the

switch to protect the contacts.

ENGINE GENERATOR SET MOUNTING

The unit’s main frame should be bolted solidly to a 4 to 6 inch

thick cement pad. The engine-generator is mounted on a sub-

frame which is attached with special shock mounts to the main

frame. This allows the engine-generator free movement without

affecting the control panel which is mounted on the main frame.

Do not shock mount the main frame. Engine vibration will be

transmitted to the control panel causing erroneous start/stop

cycles and premature control failure.

These units should be mounted to allow for ample working room

around it. Units must be installed in accordance with all local,

state and national codes. Consult your local agency having juris-

diction for specific requirements.

FUEL INSTALLATION

The fuel supply should be as close as possible to the engine.

This will reduce the installation cost of fuel runs. The informa-

tion in this manual is offered to assist you in providing the proper

fuel for your engine. However, this information is only provided to

inform you of the engine’s requirements and assist in making you

aware of the decisions you must make. In no case should the

instructions or information provided be interpreted to conflict with

any local, state or national codes. If in doubt, always consult your

local fire marshal or gas supplier.

****************

***** WARNING *****

****************

FIRE HAZARD - All fuel runs should be installed by a licensed

fuel supplier.

Connect the fuel supply to the inlet of the fuel solenoid (see

table for recommended line size). The pressure at the second-

ary demand regulator must be four to six ounces psi (per square

inch) or 7 to 11 inches W.C. (Water column) for vapor withdrawal

units. On units equipped with liquid withdrawal fuel systems full

tank pressure is plumbed to the fuellock strainer mounted on the

generator rails. The fuel converter mounted on the unit will handle

both vaporization of the fuel and pressure reduction.

INSTALLING THE FUEL LINE

** NOTICE **

The engine generator sets are properly adjusted before they leave

the factory to run on either NG (natural gas), LP (liquid propane

vapor) . LPG (liquid withdrawal propane) must be ordered spe-

cial. If it becomes necessary to change the fuel type in the field

see information on page 12.

Line Size (vapor system)

Unit location will determine the size of fuel line that is required

to supply the engine with a constant fuel pressure. Refer to the

tables below for fuel line size, fuel consumption and recommend-

ed tank size. For distances of 25 feet and over, a two regulator

fuel system is recommended. This is accomplished by installing a

primary regulator at the tank which will reduce the tank pressure

down to 10 to 15 lbs. A secondary regulator is installed to further

reduce the fuel pressure to the required six (6) oz. operating pres-

sure. This secondary regulator must be at least 10 feet from the

engine generator set. Any closer installation will require a larger

line be installed to provide a fuel reservoir. If this is not done, the

demand regulator on the unit and the pressure regulator in the

fuel line will interfere with each other. When this two (2) stage

regulator system is used, a fuel line size of 3/4 to 1 inch is gener-

ally adequate for distances up to 300 feet from the primary to the

secondary regulator. (Consult your local fuel supplier for your ex-

act requirements). The appropriate line size from the table below

is then installed from the secondary regulator to the generator set.

****************

***** WARNING *****

****************

PERSONAL DANGER - Do not use galvanized pipe in fuel line

runs. The galvanized coating can become eroded and flake off,

causing possible obstructions in the regulator or fuel valve. The

results could range from inoperative engine start to hazardous

fuel leaks.

Size of pipe normally required for generators operating on NG/LP:

up to 25 feet* over 25 feet*

PSS21

1" pipe not recommended

use a two regulator system

* Allow an additional 3 feet for each standard elbow.

Do not use ‘street ells’ (restrictive).

**** CAUTION ****

EQUIPMENT DAMAGE - Be careful when sealing gas line joints.

Excessive sealing compound can be drawn into the solenoid,

regulator or carburetor causing an engine malfunction.

FUEL PRESSURE (vapor system)

Correct fuel pressure cannot be stressed enough. The most com-

mon cause for inoperative systems is an inadequate or incorrect

fuel pressure. Performance of the engine is in direct relation to

the correctness of the fuel system. Shown below is a block dia-

gram of a typical L.P. or N.G. Installation.

This manual is related to the following products: