SPECIFICATIONS

GENERATOR

MODEL

WATTS

VOLTS

AMP

HZ

PH RPM

PSS21-3

21,000

120/240

89.0*

60

1

1800

PSS21-4

22,000 120/208 76.4** 60 3 1800

PSS21-17

22,000 120/240 66.2** 60 3 1800

PSS21-18

25,000 277/480 37.6** 60 3 1800

*Unity Power Factor - Derate 3.5% per 1000 feet elevation above

sea level.

**Power Factor .8 - Derate 3.5% per 1000 feet elevation above

sea level.

FUEL CONSUMPTION

NG (1,000 BTU/CU FT) L.P. VAPOR (2,520 BTU/CU FT)

MODEL

CF/HR BTU/HR

#/HR GAL/HR CF/HR BTU/HR

PSS21

340 340,000 16.3 3.9 136.9 344,983

L.P. TANK SIZING

Minimum required L.P. tank size for L.P. Vapor withdrawal operat-

ing at various outside temperatures given in degrees Fahrenheit

(Celsius)

TANK TEMPERATURE

MODEL

60 F(16 C) 30 F(0 C) 0 F(-18 C)

-20 F(-29 C)

PSS21

160 Gal

300 Gal 1000 Gal*

2000 Gal*

*Recommend liquid withdrawal at these temperatures.

ENGINE SPECIFICATIONS:

Refer to engine operating and maintenance instructions

** NOTICE **

Regarding Engines - This manual covers the generator portion

of these units. See the separate engine instruction manual for

engine-related problems, detailed engine information and engine

warranty.

**** CAUTION ****

EQUIPMENT DAMAGE - Be sure to check the engine oil level

frequently as specified in the engine manual.

The engine manufacturer has established an excellent worldwide

engine service organization; engine service is available from a

nearby authorized dealer or distributor; check the Yellow Pages

of the telephone directory under “engines,” or ask the dealer from

whom you purchased the power plant.

The rated power of each engine-generator is limited by the tem-

perature, altitude and all other ambient conditions specified by

the engine manufacturer. Engine power will decrease 3-1/2% for

each 1000 ft. above sea level, and will decrease an additional 1%

for each 10

o

Fahrenheit above 60

o

Fahrenheit. Units should not

be operated in ambient temperature greater than 40

o

C.

UNPACKING INSTRUCTIONS

** NOTICE **

When unpacking the generator set, be sure to inspect it care-

fully for freight loss or damage. If loss or damage is noted at the

time of delivery, require that the person making the delivery make

note of the loss or damage on the freight bill, or affix his signature

under the consignee's memo of the loss or damage. Contact the

carrier for claim procedures.

When loss or damage is noted after delivery, segregate the dam-

aged material, and contact the carrier for claim procedures.

“Concealed Damage” is understood to mean damage to the

contents of a package which is not in evidence at the time of

delivery by the carrier, but which is discovered later. The carrier

or carriers are responsible for merchandise lost or damaged in

transit. The title to goods rests with the consignee when genera-

tors are shipped FOB factory, and only the consignee can legally

file a claim.

**** CAUTION ****

EQUIPMENT DAMAGE - These units are shipped with oil, and a

50/50 mix of coolant. Be sure to check all fluid levels before oper-

ating. See engine manufacturer’s instruction manual for recom-

mended oil requirements before initial starting.

UNPACKING:

1. Carefully remove the carton.

2. After inspecting the engine-generator for external physical

damage, check for the following items packed inside the

carton:

a. Owner’s manual and wiring diagram.

b. Engine manufacturer’s instruction manual.

3. Remove main frame hold down bolts, (6).

4. Unit can now be lifted from shipping rails.

INSTALLATION

****************

***** WARNING *****

****************

PERSONAL INJURY - Before proceeding with the installation, be

sure the operation selector switch is in the "stop" position.

General Information

Note: A roof access panel has been provided to check/fill

the engine coolant. Side panels may be removed by opening

the latches on the top of the side panels.
These engine generator sets are for outdoor installation. These

units must be bolted solidly to a concrete pad. The transfer switch

is mounted next to your distribution panel inside the building.

Consult a qualified, licensed electrician or contractor to install and

wire the transfer switch. The installation must always comply with

all national, state, and local codes.