beautypg.com

D.c. electrical connections – Winco ULPSS21/E WITH DSE 7310 ENGINE CONTROL User Manual

Page 10

background image

Page 8

3025-00

60706-240

Depending on the distance, 14 to 16 gauge stranded wire should

be used. It is suggested that these wires be labeled S1 and S23.

The terminal blocks are designed to use terminal lugs on all wires

and the screws should be torqued to 9.6 in. lbs.

Note: Any relay closure can be used to start and stop this

generator. As long as the contact stays closed the engine

generator set will continue to run. Once the relay is opened

the unit will shut down and remain in the standby mode until

the remote start relay is closed again.

B - ESTOP- & ESTOP+. Remote Emergency Stop terminals.

These two terminals are shipped with a jumper installed. If your

application requires the installation of a Remote Emergency Stop

switch, remove the jumper and wire your switch to these termi-

nals.

This unit will not start and run without either the jumper

installed or a remote N/C switch installed.

C - Battery Charger Failure. Battery charger failure relay input

from remote battery charger to DSE7310 controller.

D - Remote Display Panel Interface Terminals. These interface

terminals are prewired to allow for the connection of a remote

display. This display allows for the remote annunciation of alarms

at a location such as a nurses station or a control room.

****************

***** WARNING *****

****************

Be sure Engine Generator is in the "OFF" position before you

make any DC interconnections.

**** CAUTION ****

Never run the AC and DC wiring in the same conduit.

NOTE: The right hand half of the customer connection

terminal block is for programmable inputs and outputs.

Although these terminals are wire into the DSE7310,

they are normally not programed. This terminal block

has connections for four programmable input and four

outputs along with one flex input and a ground. Con-

sult the Factory at 507-357-6831 before attempting to

program these inputs/outputs.

See the manual shipped with the Automatic Transfer Switch for

connection locations in the switch. Connections in each switch

will vary depending on the type of switch and the manufacturer.

GROUNDING

A grounding lug has been provided on the engine generator set to

ground to earth ground if required. Check with your local codes.

Generally a 6 foot copper rod driven into the earth will provide a

proper earth ground.

D.C. ELECTRICAL

CONNECTIONS

NOTE:

There are various DC connectors on the engine that have

nothing connected to them. This was done intentionally,

these connectors are for END OF LINE TESTING and other

various diagnostic tests. They are not used during normal

operations and can just be ignored.

All normal DC connections are completed on the left hand termi-

nal strip just below the engine control cabinet. See Below.

A - Customer Remote Start CONNECTIONS TERMINALS. The

two remote start leads from the Automatic Transfer Switch are

connected to the two terminals marked 1 & 23. The wire in ter-

minal labeled #1 is Battery Negative and the wire in the terminal

labeled #23 is your Remote Start lead. Closing these two leads

together will signal the DSE 7310 to go into an auto-start mode

and start up the engine generator.

Page 8

2090-00

60706-227

Depending on the distance, 14 to 16 gauge stranded wire should

be used. It is suggested that these wires be labeled S1 and S23.

The terminal blocks are designed to use terminal lugs on all

wires and the screws should be torqued to 9.6 in. lbs.

Note: Any relay closure can be used to start and stop this

generator. As long as the contact stays closed the engine

generator set will continue to run. Once the relay is opened

the unit will shut down and remain in the standby mode until

the remote start relay is closed again.

B - ESTOP- & ESTOP+. Remote Emergency Stop terminals.

These two terminals are shipped with a jumper installed. If your

application requires the installation of a Remote Emergency Stop

switch, remove the jumper and wire your switch to these termi-

nals.

This unit will not start and run without either the jumper

installed or a remote N/C switch installed..

C - Battery Charger Failure. Battery charger failure relay input

from remote battery charger to DSE7310 controller.

D - Remote Display Panel Interface Terminals. These interface

terminals are prewired to allow for the connection of a remote

display. This display allows for the remote annunciation of alarms

at a location such as a nurses station or a control room.

****************

***** WARNING *****

****************

Be sure Engine Generator is in the "OFF" position before you

make any DC interconnections.

**** CAUTION ****

Never run the AC and DC wiring in the same conduit.

Zenith ATS

The terminal markings in the Zenith ATS are marked “X1” and

“X2”. The wire labeled “Start 1” is routed to start contact "X1” and

the wire labeled “Start 23” is routed to start contact “X2”

See the manual shipped with the Automatic Transfer Switch for

connection locations in the switch. Connections in each switch

will vary depending on the type of switch and the manufacturer.

GROUNDING

A grounding lug has been provided on the engine generator set

to grounded to earth ground if required. Check with your local

codes. Generally a 6 foot copper rod driven into the earth will

provide a proper earth ground.

D.C. ELECTRICAL

CONNECTIONS

NOTE:

There are various DC connectors on the engine that have

nothing connected to them. This was done intentionally,

these connectors are for END OF LINE TESTING and other

various diagnostic tests. They are not used during normal

operations and can just be ignored.

All DC connections are completed on the terminal strip just below

the engine control cabinet.

A - Customer Remote Start CONNECTIONS TERMINALS. The

two remote start leads from the Automatic Transfer Switch are

connected to the two terminals marked 1 & 23. The wire in

terminal labeled #1 is Battery Negative and the wire in the

terminal labeled #23 is your Remote Start lead. Closing these two

leads together will signal the DSE 7310 to go into an auto-start

mode and start up the engine generator.

X1

X2

This manual is related to the following products: