TESTING POLICY:

Before any generator is shipped from the factory, it is fully

checked for performance. The generator is loaded to its full

capacity, and the voltage, current, and frequency are carefully

checked.

Rated output of generators is based on engineering tests of

typical units, and is subject to, and limited by, the temperature,

altitude, fuel, and other conditions specified by the manufacturer

of the applicable engines.

INTRODUCTION AND

DESCRIPTION

With the addition of an Automatic Transfer Switch this package

standby system includes all items necessary for a completely

automatic standby power system.

DESCRIPTION

This package power system is designed to automatically provide

standby power to unattended loads during electrical outages.

Upon an interruption of normal electrical service this package

power system's electrical control circuits will automatically start

the engine. The generator will produce electrical power and the

Automatic Transfer Switch (A.T.S.) will automatically transfer the

electrical loads to the engine-generator set. Upon restoration of

normal electrical service the A.T.S. will sense return of the normal

commercial power and retransfer the load back to normal com-

mercial power source. The engine control circuits shut off the run

signal to the engine generator set.

These package power systems consist of two major components:

1) AUTOMATIC TRANSFER SWITCH (UL LISTED)

The Automatic Transfer Switches (A.T.S.) are wall mount switches

designed for inside installation. A electronic exerciser circuit is

installed in the A.T.S. as standard equipment. The A.T.S. also

contains the power failure sensing circuitry necessary to send a

start/stop signal to the engine generator set. The following is a list

of recommended A.T.S. sizes for each model. Outdoor switches

as well as additional sizes are available, consult your sales rep for

additional information.

MINIMUM

RECOMMENDED

MODEL

VOLTAGE ATS AMPERAGE

PSS21-3 120/240

100

PSS21-4 120/208

100

PSS21-17 120/240

100

PSS21-18 277/480

100

Additional optional A.T.S. sizes are available to meet specific

needs. Contact your local WINCO dealer or the WINCO Sales

Department for a quote.

2) ENGINE/GENERATOR

This engine generator set consists of a GM 3.0L, Industrial, four

cylinder, liquid cooled engine equipped to run on L.P./N.G. fuel.

The engine operates at 1800 rpm and frequency regulation is

maintained by the electronic governor within .5 cycles variation,

from no load to rated load. The generator is a single bearing,

direct drive, rotating field design. The generator is connected to

the engine flywheel via flexible drive disks. The engine generator

is mounted in a weather proof enclosure for outside installation.

Connection boxes are provided to all customer connections (both

AC output and DC control). A

customer supplied 12 Volt, 650

CCA (BCI group 24) battery is required to complete the installa-

tion. Engine operation is controlled by a Deep Sea automatic start

control module.

ENGINE CONTROL MODULE (DSE 7310)

The DSE 7310 control modules provide integrated engine and

generator set control, protection and metering in a single package.

Microprocessor based technology allows for exact measurement,

set point adjustment, and timing functions. Front panel controls

and indicators enable quick and simple operation.

Fully configurable via PC software, allows units to be easily cus-

tomized for each application. Includes selected front panel pro-

gramming for on site changes. A wide temperature-range liquid

crystal display (132 x 64) with backlighting can be viewed under a

wide range of ambient light and temperature conditions.

DSE 7310 Control Modules have the following features:

- Local and Remote Generator Control

- Engine and Generator Protection

- CAN Bus compatible

- Programmable Logic

- Five-key Menu Navigation

- Engine Exercise Mode

- Automatic Transfer Switch Control (Mains Failure)

- User Selectable RS232 & RS485 (Remote Operation)

FUNCTIONS

DSE 7310 Control Modules perform the following functions:

Generator Protection and Metering

Generator protection includes over voltage, under voltage, under

frequency, over frequency and overload protection. Each genera-

tor protection function has an adjustable pickup and time delay

setting. Metered generator parameters include voltage, current,

real power (watts), power factor (PF)

Engine Protection and Metering

Engine protection features include oil pressure and coolant tem-

perature monitoring, over crank protection, ECU specific protec-

tion elements, and diagnostic reporting.

Metered engine parameters include, oil pressure, coolant tem-

perature, battery voltage, speed, engine load, coolant level (from

ECU), ECU specific parameters, and run-time statistics.

** NOTICE **

These units will automatically transfer if a power outage occurs

while running in an exercise mode.

This manual is related to the following products: