27 | VZ7260W Series- Installation Guide

Pband

Proportionnal band setting

Default is : 3

Adjust the proportional band used by the controller PI

control loop.

Warning. Note that the default value of 3.0 °F (1.2 °C)

gives satisfactory operation in most normal installation

cases. The use of a superior proportional band different

than the factory one is normally warranted in applications

where the controller location is problematic and leads to

unwanted cycling of the unit. A typical example is a wall

mounted unit where the controller is installed between the

return and supply air feeds and is directly influenced by

the supply air stream of the unit.

Value

F scale

Pb

d

C scale

Pb

d

3

3 F

1.7 C

4

4 F

2.2 C

5

5 F

2.8 C

6

6 F

3.3 C

7

7 F

3.9 C

8

8 F

4.4 C

9

9 F

5.0 C

10

10 F

5.6 C

Heat max

Maximum local heating

setpoint limit

Default: 90 °F (32 °C)

Maximum local occupied heating user setpoints

adjustments.

Heating setpoint range is:
40 to 90 °F (4.5 to 32.0 °C) (Increments: 0.5° or 5°)

Cool min

Minimum local cooling

setpoint limit

Default: 54 °F (12 °C)

Minimum local occupied cooling user setpoints

adjustments.

Cooling setpoint range is:

54 to 100 °F (12.0 to 37.5 °C) (Increments: 0.5° or 5°)

DisMinPo

Enable / Disable damper

minimum position

Default : On

Enables or disabled the damper minimum position

(parameter Min PO) if the controller cooling or heating

demand is not the same as the zone sequence. Example:

if controller calls for heating and the zone sequence is

Cool (sent by the VZ76xx master controller).

On = Enable Minimum Position

Off = Disable Minimum Position