beautypg.com

Viconics VZ7260X Installation Guide User Manual

Page 20

background image

20 | VZ7260W Series- Installation Guide

Get From

Controller Get From another
device configuration utility

Default value = 255
Range is: 1 to 255

Entering a new MAC address enabled an automatic
routine that automatically fetches all the required
configuration property of the current device from another
one already configured to the same required property
values. If another value than the default value of 255 is
entered, user will then be prompted to exit the
Configuration Menu.

Ex.: If you are currently configuring MAC12 and the
settings exactly match the settings of ZN MAC5, then
enter 5 as the current parameter value.

If the process is successful and all required configuration
properties have been copied, the value will revert back to
255.

If the process is NOT successful and all required
configuration properties have NOT been copied ( either
the reference device is NOT the same model number or
is offline or does not exists ) the value will revert back to
254 to indicate the failure of the process.

Leaving the Get From parameter to 255 means that
every configuration parameters has to be set manually.

RTC MAC

RTC Controller network
address
Default: 4

Master VZ76 RTU system controller to which current
VZ72 Zone controller is attached
1 to 127 (Increments: 1 or 10)

MenuScro

Menu scroll

Default: On = Scroll active

Removes the scrolling display and only presents the
room temperature to the user.

With this option enabled, no status is given for
occupancy and outdoor temperature.

On = Scroll active
Off = Scroll not active

C or F

Sets the display scale of the
controller

Default: °F

°F for Fahrenheit scale
°C for Celsius scale