24 | VZ7260W Series- Installation Guide
AO2RA/DA
RA/DA
Reverse acting or Direct acting
actuator signal for Reheat 1
Analog output signals
Default: DA signal
Changes the action of the reheat 1 analog output.
Valid only if analog reheat sequences are enabled
DA = Direct acting
0 to 100 % = 0 to 10 VDC
RA = Reverse acting
0 to 100 % - 10 to 0 VDC
VZ7260F5x00B models only
AO2 OALK
Zone’s analog reheat (AO2)
outside air temperature lockout
Default: 55°F (13°C)
Outdoor air temperature value from the RTU controller under
which the analog reheat stage will be allowed to be used.
Function will only be enabled if a valid outside air
temperature value is received at the zone.
-40 to 122 °F (-40.0 to 50.0 °C)
(Increments: 5° or 50°)
VZ7260F5x00B models only
FL TM Dp
Floating damper actuator
timing – Output BO1-BO2
Default: 1.5 minutes
Maximum stroke time of floating damper actuator
Output BO1-BO2.
0.5 to 9.0 in 0.5 minutes increment
VZ7260C5x00B models only
FL TM Rh
Floating damper actuator
timing – Output BO3-BO4
Default: 1.5 minutes
Maximum stroke time of floating damper actuator
Output BO3-BO4.
0.5 to 9.0 in 0.5 minutes increment
VZ7260C5x00B models only
FO2 OALK
Zone’s BO3-BO4 reheat
floating output outside air
temperature lockout
Default: 55°F (13°C)
Outdoor air temperature value from the RTU controller under
which the BO3-BO4 reheat output stage will be allowed to
be used
Function will only be enabled if a valid outside air
temperature value is received at the zone.
-40 to 122 °F (-40.0 to 50.0 °C) (Increments: 5° or 50°)
VZ7260C5x00B models only
BO5 OALK
Zone’s On-Off reheat (BO5)
outside air temperature lockout
Default: 32°F (0°C)
Outdoor air temperature value from the RTU controller under
which the On-Off reheat stage will be allowed to be used.
Function will only be enabled if a valid outside air
temperature value is received at the zone.
-40 to 122 °F (- 40.0 to 50.0 °C)
(Increments: 5° or 50°)