21 | VZ7260W Series- Installation Guide

Lockout Keypad lockout
levels

Default value = 0 No lock

0 = No lock
1 = Low level
2 = Medium level
3 = High level

USER KEY FUNCTIONS

LEVEL

Occupied temperature

setpoints

Local override only

Global override

access

0

1

2

3

BI1

Binary input no.1 configuration

Default: None

(None): No function will be associated with the input. Point
can still be monitored through the BACnet™ network.

(Motion NO): Used in Occupied Mode only to toggle from
the Occupied setpoints to the Stand-By setpoints when no
motion is detected for 60 minutes at the zone.

When motion is detected at the zone, the Occupied setpoint
resumes.

Contact opened = No motion detected.

Contact closed = Motion detected.

(Motion NC): Used in Occupied Mode only to toggle from
the Occupied setpoints to the Stand-By setpoints when no
motion is detected for 60 minutes at the zone.

When motion is detected at the zone, the Occupied setpoint
resumes.

Contact opened = Motion detected.

Contact closed = No motion detected.

AI4

Analog input no.4 configuration

Default: None

(None): No function will be associated with the input. Point
can still be monitored through the BACnet network.

CO2: Used when a 0-10VDC CO2 sensor is connected to
AI4 input. The value of the input signal is displayed in AI4
Dis parameter.