Viconics VZ7260X Installation Guide User Manual
Page 21

21 | VZ7260W Series- Installation Guide
Lockout Keypad lockout
levels
Default value = 0 No lock
0 = No lock
1 = Low level
2 = Medium level
3 = High level
USER KEY FUNCTIONS
LEVEL
Occupied temperature
setpoints
Local override only
Global override
access
0
1
2
3
BI1
Binary input no.1 configuration
Default: None
(None): No function will be associated with the input. Point
can still be monitored through the BACnet™ network.
(Motion NO): Used in Occupied Mode only to toggle from
the Occupied setpoints to the Stand-By setpoints when no
motion is detected for 60 minutes at the zone.
When motion is detected at the zone, the Occupied setpoint
resumes.
Contact opened = No motion detected.
Contact closed = Motion detected.
(Motion NC): Used in Occupied Mode only to toggle from
the Occupied setpoints to the Stand-By setpoints when no
motion is detected for 60 minutes at the zone.
When motion is detected at the zone, the Occupied setpoint
resumes.
Contact opened = Motion detected.
Contact closed = No motion detected.
AI4
Analog input no.4 configuration
Default: None
(None): No function will be associated with the input. Point
can still be monitored through the BACnet network.
CO2: Used when a 0-10VDC CO2 sensor is connected to
AI4 input. The value of the input signal is displayed in AI4
Dis parameter.