27 | PIR Ready VT7600 Series-Installation Guide

lockout Keypad lockout levels

Default value = 0 No lock

0 = No lock
1 = Low level
2 = High level

USER KEY FUNCTIONS

LEV

E

L

Res

u

me/

Override sche

duling

Perman

ent Occupied a

nd

Un

occ

upied S

etpoints

Temp

orary set

points usi

ng

arrows

System mo

de setting

Fan mo

de setting

Sche

dules sett

ing

Clock settin

g

Perman

ent hol

d

0

1

2

pwr del

Power-up delay

Default value = 10 seconds

On initial power up of the Terminal Equipment Controller
(each time 24 Vac power supply is removed & re-applied)
there is a delay before any operation is authorized (fan,
cooling or heating). This can be used to sequence start up
multiple units / Terminal Equipment Controller in one
location.

10 to 120 seconds

Frost pr
Frost protection enabled
Default value = Off

Off: no room frost protection
On: room frost protection enabled in all system mode at:
42 °F ( 5.6 °C )
Frost protection is enabled even in system Off mode
Off or On

On heat pump models the system mode will be forced to
EMERGENCY mode if frost protection is activated

heat max
Maximum heating setpoint
limit
Default value = 90 °F ( 32 °C )

Maximum occupied & unoccupied heating setpoint
adjustment. Heating setpoint range is:
40 to 90 °F ( 4.5 to 32.0 °C )

cool min
Minimum cooling setpoint limit
Default value = 54 °F ( 12 °C )

Minimum occupied & unoccupied cooling setpoint
adjustment. Cooling setpoint range is:
54 to 100 °F ( 12.0 to 37.5 °C )