16 | PIR Ready VT7600 Series-Installation Guide

Sequence of user menu:

OVERRIDE

RESUME

TEMPERATURE

SETPOINTS

SYSTEM

MODE

SETTING

FAN

MODE

SETTING

SCHEDULES

SETTING

CLOCK

SETTING

SCHEDULE

HOLD

Override

schd Y/N

Temperat

Set Y/N

Sys

mode

set

Y/N

Fan

mode

set Y/N

Schedule

set Y/N

Clock

set Y/N

Schedule

hold Y/N

Appears

only in

unoccupied

mode

Appears

only on

stand-alone

(Network

Ready)

models

Cancel

ovrd Y/N

Appears

only in

override

mode

Occupied setpoints adjustments

There is a default profile set in the Terminal Equipment Controller from the factory.

This enables the Terminal Equipment Controller to operate as a non-scheduling unit in
day mode operation at start up.

DEFAULT TEMPERATURE SETPOINTS:

DEFAULT MODES:

Occupied cooling setpoint = 24 °C (75 °F)

System mode = Auto

Occupied heating setpoint = 22 °C (72 °F)

Fan mode = Smart (for models with a

communication module

or scheduling network

ready models)

Fan mode = Auto (for non-scheduling

network ready models)

Unoccupied cooling setpoint = 28 °C (82°F)

Unoccupied heating setpoint = 18 °C (65°F)

DEFAULT SCHEDULES:

Fahrenheit scale

Monday through Sunday

Setpoint type = permanent

Occupied time is: 12 00 AM

Unoccupied time is: 11:59 PM