13 | PIR Ready VT7600 Series-Installation Guide

C

ONFIGURING AND

S

TATUS

D

ISPLAY

I

NSTRUCTIONS

Status display

The Terminal Equipment Controller features a two-line, eight-character display. There is a
low level backlight level that is always active and can only be seen at night.
When left unattended, the Terminal Equipment Controller has an auto scrolling display
that shows the actual status of the system.
Each item is scrolled one by one with the back lighting in low level mode. Pressing any
key will cause the back light to come on to high level.
Manual scroll of each menu item is achieved by pressing the Yes (scroll) key repetitively.
The last item viewed will be shown on the display for 30 seconds before returning to
automatic scrolling. Temperature is automatically updated when scrolling is held.

Sequence of auto-scroll status display:

ROOM

TEMPERATURE

CLOCK

STATUS

SYSTEM

MODE

SCHEDULE

STATUS

OUTDOOR

TEMPERATURE

ALARMS

x.x °C

or °F

XX % RH

Monday

12:00

AM

Sys mode

auto

Occupied

Outdoor

x.x °C or°F

Service

Sys mode

off

Occupied

hold

Frost

ON

Sys mode

heat

Unoccup

SetClock

Sys mode

cool

Filter

Sys mode

emergency

Fan

lock

Outdoor air temperature

ƒ

Outdoor air temperature display is only enabled when outdoor air temperature sensor is

connected.

A maximum range status display of 50 °C ( 122 °F ) indicates a shorted sensor.
Associated functions, such as mode lockouts and economizer function are
automatically disabled.

A minimum range status -40 °C ( -40 °F ) is not displayed and indicates a opened
sensor or a sensor not connected. Associated functions, such as mode lockouts and
economizer function are automatically disabled.


Alarms

If alarms are detected, they will automatically be displayed at the end of the status
display scroll.

During an alarm message display, the back lit screen will light up at the same time as
the message and shut off during the rest of the status display.

Two alarms maximum can appear at any given time.

The priority for the alarms is as follows: