Vtr8300 fan coil controller application guide, Bacnet, Communication wiring – Viconics VTR8300 Line Voltage Application Guide User Manual

Page 21: Wireless communication

background image

VTR8300 Fan Coil Controller

Application Guide

21

Viconics Technologies Inc.

|

9245 Langelier Blvd.

|

St.-Leonard

|

Quebec

|

Canada

|

H1P 3K9

|

Tel: (514) 321-5660

|

Fax: (514) 321-4150

028-6047-03

www.viconics.com

|

[email protected]

February 2015

©

2

01

5 V

ic

onic

s T

ec

hno

lo

gi

es

Inc

. A

ll r

ig

ht

s r

ese

rv

ed

.

AppendiX A - pAssive inFrA-red (pir) moTion deTeCTor Cover speCiFiCATions

AppendiX b - opTion neTwork wirinG iF CommUniCATinG models Are Used

+-

ref

+-

ref

+-

ref

BACnet

thermostat

1

BACnet

thermostat

2

BACnet

thermostat

3

Notes:

-

Wiring should be daisy chained

- Respect polarity
- If using 2 conductors shielded wires, connect the shield
of each feed together on the back of the controller. ONLY
ground the shield at one location. DO NOT connect the
shield to the ref terminal.

AppendiX C - ConTrollers’ oCCUpAnCy seqUenCe oF operATion sChemATiC

Setpoints

Time

Unoccupied cool

Occupied cool

Stand-by cool

72°F

76°F

80°F

Movement detected

-

Stand-by timer reset

Into Stand-by mode

-

Unoccupied timer reset

Stand-by

time

Unoccupied

time

Into Unoccupied

mode

Next movement

detected

70°F

62°F

Unoccupied heat

Occupied heat

Stand-by heat

72°F

66°F

70°F

Deadband

Deadband

Deadband

22°C

24.5°C

26.5°C

22°C

21°C

21°C

19°C

16.5°C

BACnet

®

communication

wiring

No communication wires required

Wireless Communication