Vtr8300 fan coil controller application guide, Sequence of operation and wiring, Options – Viconics VTR8300 Line Voltage Application Guide User Manual
Page 15
VTR8300 Fan Coil Controller
Application Guide
15
Viconics Technologies Inc.
|
9245 Langelier Blvd.
|
St.-Leonard
|
Quebec
|
Canada
|
H1P 3K9
|
Tel: (514) 321-5660
|
Fax: (514) 321-4150
028-6047-03
www.viconics.com
|
February 2015
©
2
01
5 V
ic
onic
s T
ec
hno
lo
gi
es
Inc
. A
ll r
ig
ht
s r
ese
rv
ed
.
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve
closes.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve
closes.
Options
•
BACnet
®
and Wireless communication models available (see
Appendix B for network wiring).
•
Can be configured for 2-pipe systems without changeover.
•
Binary inputs can be configured to control occupancy via
door or window contact, remote motion sensor, remote night
setback, or provide alarms for service or filter monitoring.