Sequence of Operation and Wiring

Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.

Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.

Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.

On Call for Cool
Cooling valve opens to maintain room temperature.

On Call for Heat
Electric heat operates to maintain room temperature. Cooling valve
closed and dehumidification is disabled.

On a Demand for Dehumidification
Dehumidification achieved via cooling coil using reheat if necessary.
Dehumidification only allowed in COOL mode or if cooling is enabled
in AUTO mode.
Dehumidification disabled if room temperature falls below low
ambient lockout temperature, which is cooling setpoint minus
configuration defined deadband value.

Options

BACnet

®

and Wireless communication models available (see

Appendix B for network wiring).

Binary inputs can be configured to control occupancy via
door or window contact, remote motion sensor, remote night
setback, or provide alarms for service or filter monitoring.

1

2
3

9

10

SOLIDSTATE

RELAY

(4-32Vdc)

(-)

(+)

SC3400E5000

VTR8300

BACnet+

BACnet-

BACnet REF

UI 16 - BI1

UI 17 - BI2

SCom

Tx / Rx

7 VDC

Com