Sequence of Operation and Wiring

Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve
closes.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve
closes.
Door Switch
Door switch automatically toggles occupancy.

Options

BACnet

®

and Wireless communication models available (see

Appendix B for network wiring).

Models available with factory installed PIR sensor.

Can be configured for 2-pipe systems without changeover.

Binary inputs can be configured to control occupancy via
door or window contact, remote motion sensor, remote night
setback, or provide alarms for service or filter monitoring.

Tx/Rx

7 Vdc

Com

1

2
3

BACnet+

BACnet-

BACnet REF

UI 16 - BI1

UI 17 - BI2

SCom

Tx / Rx

7 VDC

Com

BI2 (Door)

SCom

SC3500E5000

VTR8300