beautypg.com

Panel installation (without collar) — tcpe, Wall opening requirements – Twin City TCPE, WPB, WPD Propeller Wall Fans - IM-4800 User Manual

Page 5

background image

Twin City IM-4800

5

1. The TCPE panel fan is an axial exhauster that can

be mounted either vertically or horizontally. Figure 3

depicts a typical wall installation.

2. A typical frame is usually roughed in so that the

inside square dimension is approximately

1

2

" to

3

4

"

more than what the fan panel measures. If using the

optional wall collar the frame should be

3

4

" to 1"

more than what the fan panel measures.

3. Place the unit into the frame with the wiring hole A in

the position that is most suitable for wire to enter the

unit. Fasten the unit to the frame through the holes

provided using lag bolts. If the electrical wire will be

coming from within the wall that the TCPE is being

mounted to, run the wire through hole A by entering

it from the orifice side of the panel. This should be

done before the panel is fastened to the frame to

reduce the need of disassembly. If the wiring is not

done during the installation the motor and guard can

be removed from the panel fan without having to

actually remove the panel itself. See Figure 3. Make

sure a strain relief is attached to the wires after the

wire is pulled into position.

CAUTION: Use copper conductors only.

CAUTION: Protect all wires from sharp edges. Do

not route wire through wiring hole without a strain

relief to protect it.

4. Connect the electrical wire to a disconnect switch

and then connect the wire to the motor (an optional

speed control may be installed in series with a 115V

ODP motor and disconnect switch). See Figure 1

on Page 4. The wiring diagram for the motor is on

a label attached to the motor. Main power wiring

should be sized for the amperage shown on the data

plate attached to the fan panel.

5. Disconnect switches (Optional) are not fused; there-

fore,

the power leads must be protected at the point

of distribution in accordance with the unit data plate.

6. All TCPE motors are thermally protected. All units

must be electrically grounded in accordance with

local codes or in accordance with the NEC. A

grounding point is provided with all motors and will

be described on the wiring diagram that is attached

to the motor.

7. Supply voltage to the motor should not vary by more

than 10% of the value indicated on the unit data

plate. Phase unbalance must not exceed 2%.

WARNING: Failure of the unit due to improper line

voltage or excessive phase unbalance constitutes

product abuse. Severe damage to the unit’s electrical

components may occur.

8. Make sure unit is properly sealed around the frame

edges so that the outside elements cannot enter the

building.

PANEL

MOUNTING

FRAMING

BOLTS TO

REMOVE FAN

WIRING

HOLE ‘A’

ROT

ATION

AIRFLOW

Figure 3. Typical Installation

Figure 4. Fan Assembly Without a TCPE Wall Collar

M" (Min).

BACK OF

FAN TO

DAMPER

DAMPER

WEATHERHOOD

(EXTENDED FLANGE)

FAN

FIELD

FABRICATED

WALL COLLAR

Wall Opening Requirements

Wall opening size and the distance between propeller

and damper are two important dimensions for fan

installation. Fans mounted in or to the wall require a

different wall opening size than those mounted in collars.

Propeller-to-damper distance (M) is important to reduce

turbulence at the damper, which may lead to premature

damper failure, and to prevent the propeller blades from

hitting the actuator on motorized damper units.

TCPE

SIZE

PANEL

SQ.

WALL

OPENING

DAMPER

SIZE

'M' (MIN.)

8

13.25

13.75

10 x 10

14.0

10

15.25

15.75

12 x 12

12

18.25

18.75

15 x 15

14

21.25

21.75

18 x 18

14.0

16

23.25

23.75

20 x 20

18

25.25

25.75

22 x 22

20

27.25

27.75

24 x 24

14.0

24

30.25

30.75

27 x 27

Panel Installation (without collar) — TCPE