beautypg.com

General, Installation – Twin City Gravity Relief / Intake Ventilators - IM-4700 User Manual

Page 2

background image

2

Twin City Fan IM 4700

Receiving, Inspection & Unpacking

General Installation

Service Clearance

Unit Installation

When the equipment is received all items should be

carefully checked against the bill of lading to be sure all

crates and cartons have been received. Before accept-

ing delivery, carefully inspect each carton or crate for

visible shipping damage. If any damage is noticed, the

carrier should make the proper notation on the delivery

receipt acknowledging the damage. Make notations of all

damage on all copies of the bill of lading and have all

copies countersigned by the delivering carrier. The car-

rier should also fill out a Carrier Inspection Report. The

factory Traffic Department should then be contacted.

File claim for damage with the carrier. Physical damage

to the unit after acceptance is not the responsibility of

Twin City Fan Companies, Ltd.
Unpack each carton or crate and verify that all required

parts and proper quantities of each item have been

received. Refer to drawings for part descriptions. Report

shortages or missing items to your local representative

to arrange for replacement parts
Due to availability of carriers and truck space, it is not

possible to guarantee that all items will be shipped

together. Verification of shipments must be limited to

only those items on the bill of lading.

CAUTION: Sheet metal parts, screws, clips and similar

items inherently have sharp edges, and it is necessary

that the installer and service personnel exercise caution.
The installation of this equipment shall be in accordance

with the regulations of authorities having jurisdiction and

all applicable codes.

Adequate clearance around the unit should be kept for

safety, maintenance, and proper unit operation.
A minimum clearance of 36" to 48" is recommended

to insure proper ventilation. Unit should be installed

remote from building air exhausters to inhibit ingestion

of exhaust air into building.
Allow a minimum of 24" clearance above the unit for

removal of unit top cover. Note: Clearance may have to

be increased if using the hinged curb option.
The unit must not be installed under any obstructions.

This equipment is to be installed by an experienced

installation company and fully trained personnel.
The mechanical installation of the exhaust ventilator

consists of making final connections between the unit,

building services, and duct connections.

24"

36"

Figure 1. Service Clearances

General

1. The unit should be roof mounted only to an appro-

priately sized roof curb or duct. See "Roof Curb

Installation" on page 3.

2. The base of the curb cap should be horizontal.

Installation

1. Drill 8 holes (2 per side) into the roof curb through

the holes provided in the unit curb cap.

2. Bolt the unit to the roof curb through these holes

using

1

4

-20 self-tapping screws.

Model GRV shown