beautypg.com

Electrical connection, Check, test & start procedure – Twin City BCRFS Belt Driven Centrifugal Filtered Supply Fans - IM-4310 User Manual

Page 3

background image

Twin City IM-4310

3

Electrical Connection

1. Connect supply wiring to the disconnect switch (non-

fused standard). Check the wiring diagrams on the

motor for connections.

2. The motor is factory set at the voltage marked on

the fan nameplate. Check the line voltage with the

nameplate voltage and wiring diagrams.

3. The main power wiring should be sized for the

ampacity shown on the dataplate. Size wires in

accordance with the ampacity tables in Article 310 of

the National Electrical Code. If long wires are

required, it may be necessary to increase wire size

to prevent excessive voltage drop. Wires should be

sized for a maximum of 3% voltage drop.

CAUTION: Use copper conductors only.

CAUTION: Protect wiring from sharp edges.

Leave some slack in the line to prevent damage.

4. Disconnect switches are not fused. The power leads

must be protected at the point of distribution in

accordance with the fan dataplate.

5. On fans without a thermal protector integral to the

motor (refer to unit or motor dataplate to determine

if protector is present) a separate overload device is

required. Refer to Sections 430-32 of the N.E.C. for

sizing.

6. All units must be electrically grounded in accordance

with local codes or, in the absence of local codes,

with the latest edition of the National Electrical Code

(ANSI/NFPA 70). A ground lug is provided as stan-

dard in the unit terminal box. Size grounding conduc-

tor in accordance with Table 250-95 of the National

Electrical Code.

DO NOT use the ground lug for

connecting a neutral conductor.

7. Supply voltage to the power ventilator should not vary

by more than 10% of the value indicated on the unit

dataplate. Phase unbalance must not exceed 2%.

WARNING: Failure of motor due to operation on improp-

er line voltage or with excessive phase unbalance con-

stitutes product abuse and may cause severe damage

to the unit’s electrical components.

Check, Test & Start Procedure

1.

Disconnect power to the unit before servicing. Make

sure power is turned off and locked in the OFF

position.

2. Tighten all bolts and setscrews securely and, on belt

driven fans, check sheave alignment and belt tension.

Tighten belts if necessary. NOTE THAT ALL BOLTS,

SETSCREWS AND BELTS SHOULD BE RETIGHTENED

AFTER TWO DAYS OF INITIAL OPERATION.

3. Apply power to unit and check rotation of wheel with

the directional arrow on the unit.
WARNING: Especially check three-phase units for

rotation. For three-phase, rotation can be changed by

interchanging any two of the three line leads. If unit

is checked on temporary wiring, its should be

rechecked when permanently installed. Motor burn-out

or tripped overload protection devices are usually the

result of wrong rotation.

4. Electrical Input Check: Perform check of fan ampere

draw and verify that motor nameplate amps are not

exceeded. Take account of the service factor range

if motor is nameplated above a 1.0 service factor.

5. Fan RPM Check: Fan RPM should be checked and

verified with a tachometer.
The fan should not need balancing, as it was bal-

anced at the factory to be within stringent vibration

levels before shipment. However, there are several

things that may cause vibration, such as rough han-

dling in shipment and erection, weak foundations and

alignments.