External wiring, Fig. 21: secondary system circulator wiring – TriangleTube 110 Solo User Manual
Page 40

34
External Wiring
CH and DHW Circulator
1. The CH primary circulator is pre-wire to
the PRESTIGE Solo 120 V terminals 1,2
and 3 as shown in Fig. 20, page 32.
2. Connect the DHW circulator to the PRES-
TIGE Solo 120 V terminals 4, 5 and 6 as
shown in Fig. 20, page 32.
3. Maximum circulator continuous current
draw is 2A for each circulator.
System Circulator - Zone Valve Application
To energize the system circulator shown as
Item 12 in Fig. 10 page 21 reference Fig. 21.
Installer to provide a Transformer / Relay such
as Honeywell R8285 or equivalent and Zone
Valves with isolated end switch such as
Honewell V8043 or equivalent.
External Modulating Control
The PRESTIGE Solo firing rate can be con-
trolled by an external modulating boiler con-
troller. See page 32 for wiring and Page 54 for
control module setup.
Outdoor Reset Control
1. The PRESTIGE Solo may operate with a
variable boiler operating temperature using
the Triangle Tube outdoor sensor, see pages
49 through 51 for installation and setup.
If the installer opts for a fixed operating
temperature for the boiler system, the
outdoor sensor is not required and
should not be installed.
Additional 24V Limit Wiring
The PRESTIGE Solo provides 24V terminal
connections for additional limit controls as
shown in Fig. 20, page 32. These limit termi-
nal connections will provide a "hard" lockout
requiring a manual reset of the PRESTIGE
Solo control, or a “soft” lockout in which the
PRESTIGE Solo will automatically reset.
NOTICE
24 V
Transformer
by Others
Honeywell V8043
Zone Valves
or Equivalent
Honeywell R8285D
Transformer / Relay
or Equivalent
24V Terminal Strip
System Circulator
24V Low Voltage Wiring
120V High Voltage Wiring
Room Thermostats
H
N
120V
R
C
G
1
3 4
6
7
8
To Prestige
Fig. 21: Secondary System Circulator Wiring