beautypg.com

TriangleTube 110 Solo User Manual

Page 14

background image

8

Combustion Air and Venting

-

Not less than the sum of the areas of all
vent connectors in the space.

Two Permanent Openings Method.

Two permanent openings, one commencing
within 12 in. of the top and one commencing
within 12 in. of the bottom of the enclosure,
shall be provided. The openings shall commu-
nicate directly, or by ducts, with the outdoors
or spaces that freely communicate with the out-
doors, as follows:

-

Where directly communicating with the
outdoors or where communication to the
outdoors is through vertical ducts, each
opening shall have a minimum free area
of 1 sq. in./4000 Btu/hr of total input rat-
ing of all equipment in the enclosure.
See Fig.3.

-

Where communicating with the out-
doors is through horizontal ducts, each
opening shall have a minimum free
area of not less than 1 sq.in./2000
Btu/hr of total input rating of all equip-
ment in the enclosure. See Fig. 4.

Combination of Indoor and Outdoor
Combustion Air

Indoor Openings: Where used, openings con-
necting the interior spaces shall comply with
the Indoor Combustion Air section on page 7.

All Combustion Air from Outdoors
Through One Permanent Air
Opening

Fig. 2:

All Combustion Air from Outdoors
Through Ventilated Attic

Fig. 3:

All Combustion Air from Outdoors
through Horizontal Ducts

Fig. 4: