Toa FS-971 SERIES User Manual

Page 7

background image

Suitable zone numbers

Under 80 zones

90 – 110 zones

120 – 150 zone

160 – 220 zones

230 – 330 zones

7

110 zones

1.2 A

2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity

When a large current is consumed depending on the number of connected remote control units and zones,
the JP-0410's fuses (Emergency Remote Control 1 and 2 fuses) for remote control units must be replaced.

The following table shows the relationship between current consumption and zone numbers per remote
control unit.

10 zones

0.3 A

20 zones

0.4 A

30 zones

0.48 A

40 zones

0.58 A

50 zones

0.66 A

60 zones

0.76 A

70 zones

0.84 A

80 zones

0.94 A

90 zones

1.02 A

100 zones

1.12 A

220 zones

2.2 A

120 zones

1.3 A

130 zones

1.38 A

140 zones

1.48 A

150 zones

1.56 A

160 zones

1.66 A

170 zones

1.74 A

180 zones

1.84 A

190 zones

1.92 A

200 zones

2.02 A

210 zones

2.1 A

330 zones

3.18 A

230 zones

2.28 A

240 zones

2.38 A

250 zones

2.46 A

260 zones

2.56 A

270 zones

2.64 A

280 zones

2.74 A

290 zones

2.82 A

300 zones

2.92 A

310 zones

3.0 A

320 zones

3.1 A

EMG RM1

1.6A

EMG RM2

EMG OFF

GEN RM

CONTROL

1.6A

0.5A

0.5A

3A

10

9

8

7

For "1 EMG RM 24V"

For "2 EMG RM 24V"

JP-0410 fuse holder

EF

(FA)

EMG
ACTI

CPU

OFF

C

H

GND

24V

GND

24V

BATT 1 BATT 2

MONITOR

1 EMG RM 24V 2 EMG RM 24V

DS CHECK

C1

H1

C2

H2

C3

H3

C4

H4

(-)1

(+)1

(-)2

(+)2

(-)3

(+)3

EMG REMOTE BUS

EMG REMOTE AUDIO IN

JP-0410 upper row
terminal block

Fuse capacity

2 A

2.5 A

3.15 A

4 A

5 A

Part name

Fuse 250V 2A 5x20 time lag

Fuse 250V 2.5A 5x20 time lag

Fuse 250V 3.15A 5x20 time lag

Fuse 250V 4A 5x20 time lag

Fuse 250V 5A 5x20 time lag

Part code number

115-40-089-00

115-40-090-80

115-40-091-90

115-40-092-20

115-40-093-70

Two circuits of fuse/power supply terminal combinations are provided for the remote control unit. The
maximum permissible current is 5 A for both circuits put together.

When replacing the fuse for the remote control unit, use the "time-lag" type fuse. Note that the fuse exceeding
5 A cannot be used because the fuse holder is 5 A in maximum rating.