110 zones
1.2 A
2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity
When a large current is consumed depending on the number of connected remote control units and zones,
the JP-0410's fuses (Emergency Remote Control 1 and 2 fuses) for remote control units must be replaced.
The following table shows the relationship between current consumption and zone numbers per remote
control unit.
10 zones
0.3 A
20 zones
0.4 A
30 zones
0.48 A
40 zones
0.58 A
50 zones
0.66 A
60 zones
0.76 A
70 zones
0.84 A
80 zones
0.94 A
90 zones
1.02 A
100 zones
1.12 A
220 zones
2.2 A
120 zones
1.3 A
130 zones
1.38 A
140 zones
1.48 A
150 zones
1.56 A
160 zones
1.66 A
170 zones
1.74 A
180 zones
1.84 A
190 zones
1.92 A
200 zones
2.02 A
210 zones
2.1 A
330 zones
3.18 A
230 zones
2.28 A
240 zones
2.38 A
250 zones
2.46 A
260 zones
2.56 A
270 zones
2.64 A
280 zones
2.74 A
290 zones
2.82 A
300 zones
2.92 A
310 zones
3.0 A
320 zones
3.1 A
EMG RM1
1.6A
EMG RM2
EMG OFF
GEN RM
CONTROL
1.6A
0.5A
0.5A
3A
10
9
8
7
For "1 EMG RM 24V"
For "2 EMG RM 24V"
JP-0410 fuse holder
EF
(FA)
EMG
ACTI
CPU
OFF
C
H
GND
24V
GND
24V
BATT 1 BATT 2
MONITOR
1 EMG RM 24V 2 EMG RM 24V
DS CHECK
C1
H1
C2
H2
C3
H3
C4
H4
(-)1
(+)1
(-)2
(+)2
(-)3
(+)3
EMG REMOTE BUS
EMG REMOTE AUDIO IN
JP-0410 upper row
terminal block
Fuse capacity
2 A
2.5 A
3.15 A
4 A
5 A
Part name
Fuse 250V 2A 5x20 time lag
Fuse 250V 2.5A 5x20 time lag
Fuse 250V 3.15A 5x20 time lag
Fuse 250V 4A 5x20 time lag
Fuse 250V 5A 5x20 time lag
Part code number
115-40-089-00
115-40-090-80
115-40-091-90
115-40-092-20
115-40-093-70
Two circuits of fuse/power supply terminal combinations are provided for the remote control unit. The
maximum permissible current is 5 A for both circuits put together.
When replacing the fuse for the remote control unit, use the "time-lag" type fuse. Note that the fuse exceeding
5 A cannot be used because the fuse holder is 5 A in maximum rating.