EM-40-SM Service Manual
Mode 4 and 5 – Outdoor Reset and Setpoint Operation - Adjust Menu (3 of 3)
Item Field
Range
Description
Access
Setting
0:10 to 5:00 min
MINIMUM ON TIME
Select the minimum amount of time that
the stage contact must remain on before it
is allowed to turn off.
Note: This setting is only available when
STAGE MODE is set to P.
Factory
0:10 to 5:00 min
MINIMUM OFF TIME
Select the minimum amount of time that
the stage contact must remain off before it
is allowed to turn back on.
Note: This setting is only available when
STAGE MODE is set to P.
Factory
OFF, 0:20 to
9:55 min, On
PUMP DELAY
Select the boiler pump purge time after
shutting off the boiler.
Factory
35 to 100°F
(2 to 38°C),
OFF
WARM WEATHER SHUT DOWN
Select the heating system warm weather
shut down for outdoor reset operation. Heat
demands are ignored once the outdoor air
temperature exceeds this setting.
Factory
Installer
°F or °C
TEMPERATURE UNITS
Select to display temperature in degrees
Fahrenheit or in degrees Celsius.
Factory
Installer
After the last item, the control returns to the first item in the menu.
ADJUS
T MENU
Default
Setting 65˚F