Adjus t menu – Slant/Fin EM-10 Service Manual User Manual
Page 24

24
EM-40-SM Service Manual
Mode 4 and 5 – Outdoor Reset and Setpoint Operation - Adjust Menu (1 of 3)
Item Field
Range
Description
Access
Setting
1 to 8
MODE
Select the operating mode for the control.
Factory
Installer
PId or P
STAGE MODE
Select the staging operation to be either
automatic or manual.
(PId = automatic)
(P = proportional)
Factory
Installer
OFF,
70 to 220°F
(21 to 104°C)
BOILER TARGET
Select the boiler target temperature while
a setpoint demand is present.
Factory
Installer
35 to 85°F
(2 to 29°C)
OUTDOOR START
Select the outdoor starting temperature
used in the reset ratio for the heating
system. Typically set to the desired building
temperature.
Factory
Installer
-60 to 32°F
(-51 to 0°C)
OUTDOOR DESIGN
Select the outdoor design temperature used
in the reset ratio for the heating system. Set
to the coldest annual outdoor temperature
in the local area.
Factory
Installer
35 to 150°F
(2 to 66°C)
BOILER START
Select the starting water temperature used
in the reset ratio calculation for the heating
system. Typically set to the desired building
temperature.
Factory
Installer
70 to 220°F
(21 to 104°C)
BOILER DESIGN
Select the boiler design water temperature
used in the reset ratio calculation for the
heating system. Set to the boiler water
temperature required to heat the building on
the coldest annual outdoor temperature.
Factory
Installer
120 to 225°F
(49 to 107°C)
BOILER OUTLET MAXIMUM
S e l e c t t h e m a x i m u m b o i l e r o u t l et
temperature. Exceeding this temperature
shuts off the boiler.
Factory
ADJUS
T MENU
Continued on next page.
The Program menu items are the programmable settings
used to operate the system. Press and hold all three
buttons simultaneously to enter the Program menu
Item
Item
Change Value
Next Item
Enter Adjust Menu
Default
Setting 4