EM-40-SM Service Manual
Mode 1 and 2 – Two Setpoint Operation - Adjust Menu (1 of 2)
Item Field
Range
Description
Access
Setting
1 to 8
MODE
Select the operating mode for the control.
Factory
Installer
PId or P
STAGE MODE
Select the staging operation to be either
automatic or manual.
(PId = automatic)
(P = proportional)
Factory
Installer
OFF,
70 to 220°F
(21 to 104°C)
BOILER TARGET 1
Select the boiler target temperature while a
heat demand is present.
Factory
Installer
OFF,
70 to 220°F
(21 to 104°C)
BOILER TARGET 2
Select the boiler target temperature while a
setpoint demand is present.
Factory
Installer
120 to 225°F
(49 to 107°C)
BOILER OUTLET MAXIMUM
S e l e c t t h e m a x i m u m b o i l e r o u t l et
temperature. Exceeding this temperature
shuts off the boiler.
Factory
120 to 225°F
(49 to 107°C),
OFF
BOILER MAXIMUM
S e l e c t t h e m a x i m u m b o i l e r t a r g et
temperature.
Factory
OFF,
80 to 180°F
(27 to 82°C)
BOILER MINIMUM
S e l e c t t h e m i n i m u m b o i l e r t a r g e t
temperature.
Factory
0:00 to 3:00 min
(1 second
increments)
FIRE DELAY
(Not valid for electric boiler application)
Select the amount of time required
for combustion pre-purging, ignition
a n d t h e f l a m e t o b e e s t a b l i s h e d .
Note: This setting is only available when
STAGE MODE is set to PId.
Factory
1 (Lo) or
2 (Med) or
3 (Hi)
BOILER MASS
Select the thermal mass of the boiler.
Note: This setting is only available when
STAGE MODE is set to PId.
Factory
Installer
ADJUS
T MENU
Continued on next page.