SilentKnight SK-Beam / SK-Beam-T Addressable Beam Smoke Detector w/Test User Manual
Page 9

SK-400-007
9
I56-3433-001R
These steps include:
1. verify all wiring connections and appropriate power is applied to the
detector.
2. verify that the optical line of sight is free from obstructions and reflective
objects.
3. Apply the maintenance procedure in this manual. Repeat the test proce-
dure. If the detector still fails the test procedure proceed with step 4.
4. Repeat the alignment procedure in this manual. If the alignment proce-
dure is successful repeat the test procedure. If the detector still fails the
test it should be returned for repair.
NOTE: For the SK-Beam-T, the external power supply must be connected for
the test switch to work.
mAintenAnCe
NOTE: Before cleaning the detector, notify the proper authorities that the
smoke detector system is undergoing maintenance, and therefore the system
will be temporarily out of service. Disable the zone or system undergoing
maintenance to prevent unwanted alarms.
1. Carefully clean the outer housing lens face. A damp soft cloth with a mild
soap may be used. Avoid products with solvents or ammonia.
2. Carefully clean the reflector. A damp soft cloth with a mild soap may be
used. Avoid products with solvents or ammonia.
3. Notify the proper authorities that the system is back on line.
pAINTING
The outer aesthetic ring may be painted using a spray or brush type paint of
appropriate type. See specification section of this manual for paint types.
NOTE: Never paint the flat lens surface of the outer housing.
SpECIAL NOTE REGARDING SMOKE DETECTOR GUARDS
Smoke detectors are not to be used with detector guards unless the combina-
tion has been evaluated and found suitable for that purpose.