Sequence of Operation with Optional Fill and Drain

and/or Freeze Protection Kits
Applies to: Float and Pump System with Optional Fill

and Drain Kit (Option CT1, CT2, or CT3)

1) Call for cooling.

2) 2-way valve is energized and closes B to A.

3) 3-way valve energized, opening B to C & closing A to C.

4) During no call for cooling, valves return to normal state.

Applies to: AquaSaver Timed Water System with

Optional Freeze Protection (Option CT5)

1) Call for cooling.

2) 3-way valve energized, opening B to C & closing A to C.

3) If outside air temperature drops below freeze protec-

tion controller setting, 3-way valve is de-energized and

AquaSaver 24V solenoid valve remains energized for

eight minutes to allow complete system water drainage.

4) During no call for cooling, 3-way valve returns to normal

state.

Applies to: Float and Pump System with Optional Fill

and Drain Kit (Option CT1, CT2, or CT3) and Freeze

Protection (Option CT6)

1) Call for cooling.

2) 2-way valve is energized and closes B to A.

3) 3-way valve is energized opening B to C & closing A to

C.

4) If outside air temperature drops below freeze protection

controller setting, valves return to normal state.

5) During no call for cooling, valves return to normal state.

Left Side View

Evaporative

Cooling Module

(Outdoor installation illustrated)

Inlet Water

Connection

Overflow Fitting

3/4” male NPT tapped

with 1/2” female NPT

Drain Fitting

3/4” male NPT tapped

with 1/2” female NPT

2-WAY SOLENOID VALVE

(normally open)

1/2” female NPT

(A 2-way valve is in

Options CT1, CT2, and CT3.

Option CT6 requires

Option CT1, CT2, or CT3.)

To Drain

3-WAY SOLENOID VALVE (valve is suitable for a

maximum close-off pressure differential of 25 psi

and a system static pressure of 300 psi) - 1/2” NPT,

2-position spring return (normally closed at B port)

(A 3-way valve is in Options CT1, CT2, CT3, and CT5.

Option CT6 requires Option CT1, CT2, or CT3.)

Actuator must be above the

valve body when mounted

in horizontal piping.

Roof

Water Inlet

Field-supplied

Service Valve

Field-supplied Pressure

Regulator (if required)

A

A

B

B

C

= Field-installed Water Piping

Code

393 -

3-Way

Valve

Code 394 -

Temperature Controller

Code 395 -

Relay

Codes 396

& 397 -

Relay and

Socket

www.ReznorHVAC.com; (800) 695-1901

©2015 Reznor LLC, All rights reserved.

Trademark Note: Reznor

®

and PREEVA

®

are registered in at least the United

States. All other trademarks are the property of their respective owners.

Form P-PREEVA Version 01-15

Optional Evaporative

Cooling Module

(cont’d)

Evaporative Cooling

Module Optional Fill

and Drain Kits and

Freeze Protection

Controls

CODE Description

In Opt

P/N

392 2-Way Solenoid Valve

(field-installed)

115V CT1

50032

208V CT2

50297

230V CT3

50299

393 3-Way Solenoid Valve

(field-installed)

115V CT1

50033

208V CT2

50296

230V CT3

50298

24V

CT5

178677

394 Temperature Controller* CT5 and CT6 126170

395 Time Delay Relay*

CT5

89661

396 Relay*

CT5

211411

397 Relay Socket*

CT5

211415

*Factory-installed in the AquaSaver junction box.

®