Form I-VR-OA, P/N 205406 (Rev 3), page

Applies to:

Tubular Infrared Model VR (60 Hz or 50 Hz)

and Model GVR (50 Hz)

Installation of Combustion Air

Inlet Kit, Option DE2

Form I-VR-OA (Version A)

Obsoletes Form I-VR-OA

An optional combustion air inlet kit is required when the application requires

combustion air from outside the building. Outside combustion air should be

supplied (1) if the building atmosphere has negative pressure; (2) if the build-

ing atmosphere is dirty or dusty; (3) if the building atmosphere contains any

substance that will cause toxic gas when passed through a flame; or (4) if the

heater is being installed in a tightly closed room that does not provide required

air for combustion.
Do not install outside combustion air inlet on an unvented heater.
The kit includes components listed below. The air inlet cover and flexible sec-

tion of pipe connect directly to the burner/control box and extend a maximum

of three feet (.9M). The pipe between the expandable pipe and the terminal cap

is field-supplied.

Application and

Kit Components

FIGURE - Outside

Air Kit, Option DE2

Components

2

3

4

(Relay has wires attached.)

5

Maximum Length

Select a location for the

outside air terminal so

that the maximum length

including the equivalent

length for elbows is not

exceeded.

Kit P/N

204785

204786

Application/BTUH Size (VR is available

in 60 Hz or 50 Hz; GVR is 50 Hz only.)

50, 75, 00, & 25 (all 50 or

60 Hz); 50 (60 Hz only)

50 and 75 (50 Hz only);

75 and 200 (60 Hz only)

Item Components

Qty

P/N

P/N

1

Combustion Air Inlet Cover

1

204783

204784

2

Inlet Air Cap

1

120726

204782

3

Flex Pipe, 40” (1016mm) long 1

120729, 4” diameter

204956, 5” diameter

4

Relay Assembly

1

205540 (Relay P/N 103319 w/ three 6” wires w/ terminals)

Hardware Bag:

5

1/2” Wide Worm Drive

Clamp, stainless

2

102716, 3-5/8” to 4-1/2”

diameter range

155320, 4-5/8” to 5-1/2”

diameter range

(Not illustrated)

Drill Fixture

1

204615

204617

#8-32x1/2” long screw

2

195638 (for attaching combustion air inlet cover)

#6x5/8” long round head

phillips Rolox

2

110076 (for attaching relay)

Orange Wire Nut

1

16354

Yellow Wire Nut

1

16355

Wiring Diagram Label

1

205526

®

Maximum Length of Outside Combustion Air Inlet Pipe

Type of Inlet Air

Pipe

BTUH Size

Hz

Maximum

Length

Equivalent Length for

90° Elbow 45° Elbow

* 4” Smooth Wall

50, 75, 100

50 or 60

80 ft (24.3M) 10 ft (3M)

5 ft (1.5M)

125

60 ft (18.3M) 10 ft (3M)

5 ft (1.5M)

150

60

5” Smooth Wall

150

50

175

50 or 60

200

60

* 4” Corrugated or

Flexible

50, 75, 100

50 or 60

40 ft (12.2M)

N/A

N/A

125

30 ft (9.1M)

N/A

N/A

150

60

5” Corrugated or

Flexible

150

50

175

50 or 60

200

60

*Assumes the use of three feet (.9M) of flexible pipe at the combustion air inlet on the

burner/control box