HORIZONTAL APPLICATION

7.

Secure power exhaust to side face of
the horizontal duct over the precut
hole with screws provided. Support
assembly as required. Caulk all
seams to ensure a leak free seal.

8.

Install barometric relief hood in front of
exhaust air opening.

9.

Reconnect power to the unit. Energize
economizer to an opening greater
t h a n w h a t t h e p o w e r e x h a u s t
activation switch is set for to verify
proper accessory operation.

BAROMETRIC RELIEF HOOD

EXHAUST AIR OPENING

RETURN DUCT

SUPPLY DUCT

NEIPE07

SUPERSEDES 09-02-08
JULY 14, 2009

CUT OPENING

INSTALLATION

INSTRUCTION

INSTALLATION INSTRUCTIONS FOR

POWER EXHAUST USED WITH Q5SN AND

R4G(M,N)-090/120 (R-22) UNITS AND P6SP, R6SP,

Q6SP-072/120 (R410A) UNITS

Return Duct Size:
6 and 7.5 Ton Models - 31 ½" W x 12

3

8

" H

10 Ton Models - 31 ½" W x 19" H

Horizontal duct at unit requires 1" top and
bottom flanges and 2 ½" side flanges for proper
mounting and sealing to economizer and unit.

Power Exhaust Air Opening:
6 and 7.5 Ton Models - 30" W x 11 ½" H
10 Ton Model - 30" W x 18" H

Figure 4