beautypg.com

Reznor P6SP Option - Installation - Power Exhaust - Light Commercial User Manual

Installation instruction, Warn ing

background image

INSTALLATION

INSTRUCTION

INSTALLATION INSTRUCTIONS FOR

POWER EXHAUST USED WITH Q5SN AND

R4G(M,N)-090/120 (R-22) UNITS AND P6SP, R6SP,

Q6SP-072/120 (R410A) UNITS

Fig ure 1

CONTROL ACCESS

EXHAUST HOOD

EXHAUST MOTOR & FAN

Figure 2

FORM # 610A-0709 (610A-0808)

I - Ship ping and Pack ing List

Package 1 of 1 contains:

1 - Power Exhaust Assembly
1 - Barometric Relief Hood
6 - #10 x ½ x 16 Hex Tec
1 - End Switch
1 - 1 ½" Wire Grommet

Check contents for shipping damage. Contact the last
carrier immediately if any shipping damage is found.

II - Ap pli ca tion

Power exhaust can be used in down flow and horizontal
economizer applications. This power exhaust is designed
to relieve excess pressure that may occur with
economizers or certain building conditions. All fan motors
are recognized by UL. Permanently lubricated ball bearing
and motor overload protection are standard.

FILTER ACCESS

Read these instructions in their entirety before proceeding with the installation of the power exhaust unit, control
components, and its wiring.

6, 7.5 and 10 Ton Pack age Sys tems - R4GM, R4GN, R6GP, P4SM, P4SN, P6SP,Q5SN, and Q6SP Se ries

Unit Model

Nordyne

Part No.

Volts

Phase

No. of

Fans

HP

High Speed

FLA

Fuse

MCA

2

MOP

2

CFM

1

RPM

R6GP and P6SP- 072* Se ries

R4GM, R4GN,and R6GP - 090* Se ries

P4SM, P4SN,and P6SP - 090* Se ries

547867

208

3

1

0.5

2350

1725

2.50

6A

3.13

5.63

230

3.00

6A

3.75

6.75

547868

460

3

1

0.5

2350

1725

1.50

3A

1.88

3.38

547890

575

3

1

0.5

2385

1750

0.88

2A

1.10

1.98

R4GM, R4GN,and R6GP- 120* Se ries

P4SM, P4SN,and P6SP- 120* Se ries

Q5SN and Q6SP - 090*/120* Se ries

547876

208

3

1

0.75

4900

1140

4.00

9A

5.00

9.00

230

4.00

9A

5.00

9.00

547877

460

3

1

0.75

4900

1140

2.00

4A

2.50

4.50

547891

575

3

1

0.75

4900

1140

1.50

3A

1.88

3.38

Note:
1. CFM is per fan curve @ 0.1" w.c. ex ter nal static pres sure
2. Applicable to R6GP, P6SP, Q5SN, and Q6SP Models only.

This kit is to be installed by a qualified service
technician in accordance with these instructions and
all codes having jurisdiction. Failure to follow these
instructions could result in serious injury, property
damage, or death. These instructions are primarily
intended to assist qualified individuals experienced in
the proper installation of this appliance. Some local
codes require licensed installation/service personnel
for this type of equipment.

Warn ing:

ECONOMIZER INSTALLED

ECONOMIZER BAROMETRIC RELIEF HOOD

III - In stal la tion and Elec tri cal Con nec tions

1.

Disconnect all power to unit.

2.

Cut and discard wire tie securing wire bundle to the damper motor

Table 1