beautypg.com

Warning – Reznor R8HE Option - Installation - Gas/High Alt. Conv. User Manual

Page 3

background image

3

2. Check all gas connections for leaks with a soap and

water solution. If the solution bubbles there is a gas

leak which must be corrected.

3. Turn on the electrical power to the appliance.

4. Place the gas valve ON / OFF switch to the ON position.

See Figure 2.

5. Set the thermostat above room temperature to begin

the heating cycle of the furnace.

6. Check that the furnace ignites and operates properly.

Refer to the installation instructions provided with the

unit for the normal operating sequence.

7. After ignition, visually inspect the burner assembly to

ensure that the flame is drawn directly into the center of

the heat exchanger tube. In a properly adjusted burner

assembly, the flame color should be blue with some light

yellow streaks near the outer portions of the flame.

NOTE: The ignitor may not ignite the gas until all air is

bled from the gas line. If the ignition control locks out,

turn the thermostat to its lowest setting and wait one

minute then turn the thermostat above room temperature

and the ignitor will try again to ignite the main burners.

This process may have to be repeated several times

before the burners will ignite. After the burners are lit,

check all gas connections for leaks again with the soap

and water solution.

Measuring the Manifold Pressure

The manifold pressure must be measured by installing a

pressure gauge (Manometer, Magnehelic Meter, etc.) to

the outlet end of the gas valve as follows:

1. Turn off all electrical power to the appliance.

2. Shut OFF the gas supply at the manual shutoff valve

located outside of the appliance.

3. Using a 3/16” Allen wrench, remove the manifold

pressure tap plug located on the outlet side of the gas

valve. See Figure 2.

4. Install an 1/8” NPT pipe thread fitting, that is compatible

with a Manometer or similar pressure gauge.

5. Connect the Manometer or pressure gauge to the

manifold pressure tap.

6. Set the room thermostat above room temperature to

start the furnace.

7. Allow the furnace to operate for 3 minutes and then

check the manifold pressure. Compare the measured

value with the value shown in Table 2 (page 4). If the

manifold pressure is not set to the appropriate pressure,

then it must be adjusted.

Adjusting the Manifold Pressure

NOTE: Adjustments must be made to both LOW & HIGH

fire settings when converting two-stage gas valves. Refer

to Table 2 for manifold pressures.
1. Remove the cap screw (Figure 2, page 4).

2. Using a screwdriver or Allen wrench (where appropriate),

slowly turn the adjustment screw till the appropriate

manifold pressure listed in Table 2 is achieved.

NOTE: Turning the screw clockwise increases the

pressure, turning the screw counter-clockwise

decreases the pressure. To prevent the screw from

GAS PRESSURE ADJUSTMENT

Measuring the Supply Gas Pressure

1. Turn OFF the gas supply at the manual valve located

on the outside of the unit.

2. Using a 3/16” Allen wrench, remove the plug from the

inlet pressure tap (INLET side of gas valve). See Figure

2.

3. Install an 1/8” NPT pipe thread fitting, that is compatible

with a Manometer or similar pressure gauge.

4. Connect the Manometer or pressure gauge to the Inlet

Pressure Tap.

5. Turn ON the main gas supply at the manual valve.

6. Check and adjust the incoming gas line pressure to

11.0-14.0 inches Water Column for LP/Propane gas.

7. Turn OFF the gas supply at the manual valve.

8. Disconnect the Manometer or pressure gauge.

9. Remove the NPT fitting and reinstall the INLET pressure

tap plug. Hand tighten the plug first to prevent cross-

threading. Tighten with 3/16 Allen wrench.

Lighting & Adjustment of the Appliance

WARNING:

FIRE OR EXPLOSION HAZARD

Failure to follow safety warnings exactly could

result in serious injury or property damage.
Never test for gas leaks with an open flame. Use

a commercially available soap solution made

specifically for the detection of leaks to check

all connections. A fire or explosion may result

causing property damage, personal injury or

loss of life.

1. Turn ON the manual gas valve, located on the outside

of the unit to the ON position.

by the larger springs from the kit. The LP/Propane
springs for both HIGH & LOW fire are the same
size, shape and color. See Figure 2 (page 4).

• Use only a Torx-25 or 3/16” flathead screwdriver

when removing adjustment screws or during
pressure adjustment.

1. Remove the HIGH fire cap screw. See Figure 2.

2. Remove and discard the HIGH fire adjustment screw

from the gas valve.

3. Remove the spring from the gas valve and discard.

4. Install a larger spring from the conversion kit.

5. Install a new adjusting screw from the kit.

6. Repeat steps 1 - 5 for replacement of the LOW fire

spring and adjustment screw.

7. Check and adjust the regulator setting. See Gas Pressure

Adjustment Section.

8. Reinstall the cap screws on the HIGH and LOW

regulators. Plastic replacement cap screws are provided

in the conversion kit.

9. Affix the yellow label from the spring conversion kit to

the gas valve.