Reznor JS4BD (3ph) Unit Installation Manual User Manual
Page 9

9
Suct.
press.
outdoor temperature (°F)
70
75
80
85
90
95
100
105
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
131
264
143
133
265
146
290
145
135
267
149
292
148
317
147
137
268
153
293
151
318
149
343
148
139
269
156
294
154
319
152
344
151
369
150
141
295
157
320
155
345
154
370
153
395
151
143
322
158
347
157
372
156
397
154
422
153
145
348
160
373
158
398
157
423
156
448
154
147
349
163
374
161
399
160
424
159
449
157
149
376
164
401
163
425
162
450
161
151
402
165
427
164
452
163
153
428
167
453
166
155
454
168
157
table 3. charging table for S4Bd-036 Series (3 ton units) - orifice matches
table 4. charging table for S4Bd-048 Series (4 ton units) - orifice matches
Suct.
press.
outdoor temperature (°F)
70
75
80
85
90
95
100
105
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
124
260
132
126
261
136
284
136
128
262
139
285
139
308
139
130
263
142
286
142
309
142
332
142
132
264
145
287
145
310
146
333
146
356
145
134
288
148
311
149
334
149
357
149
380
149
136
312
152
335
152
358
152
381
152
404
152
138
336
155
359
155
382
155
405
155
428
155
140
337
158
360
158
383
158
406
159
429
159
142
361
161
384
161
407
162
430
162
144
385
164
408
164
431
165
146
409
167
432
168
148
433
170
150
legend
Shaded boxes indicate flooded conditions.
Rated design values. The suction pressure will be lower than design value if outdoor air flow, entering
dry bulb, or entering wet bulb temperatures are lower than design.
noteS:
1. All pressures are listed psig and all temperatures in °F
2. Discharge temperatures GREATER than charted values indicate an UNDERCHARGED system.
3. Discharge temperatures LESS than charted values indicate an OVERCHARGED system.