Suct.

press.

outdoor temperature (°F)

70

75

80

85

90

95

100

105

liq.

press.

dis.

temp.

liq.

press.

dis.

temp.

liq.

press.

dis.

temp.

liq.

press.

dis.

temp.

liq.

press.

dis.

temp.

liq.

press.

dis.

temp.

liq.

press.

dis.

temp.

liq.

press.

dis.

temp.

131

264

143

133

265

146

290

145

135

267

149

292

148

317

147

137

268

153

293

151

318

149

343

148

139

269

156

294

154

319

152

344

151

369

150

141

295

157

320

155

345

154

370

153

395

151

143

322

158

347

157

372

156

397

154

422

153

145

348

160

373

158

398

157

423

156

448

154

147

349

163

374

161

399

160

424

159

449

157

149

376

164

401

163

425

162

450

161

151

402

165

427

164

452

163

153

428

167

453

166

155

454

168

157

table 3. charging table for S4Bd-036 Series (3 ton units) - orifice matches

table 4. charging table for S4Bd-048 Series (4 ton units) - orifice matches

Suct.

press.

outdoor temperature (°F)

70

75

80

85

90

95

100

105

liq.

press.

dis.

temp.

liq.

press.

dis.

temp.

liq.

press.

dis.

temp.

liq.

press.

dis.

temp.

liq.

press.

dis.

temp.

liq.

press.

dis.

temp.

liq.

press.

dis.

temp.

liq.

press.

dis.

temp.

124

260

132

126

261

136

284

136

128

262

139

285

139

308

139

130

263

142

286

142

309

142

332

142

132

264

145

287

145

310

146

333

146

356

145

134

288

148

311

149

334

149

357

149

380

149

136

312

152

335

152

358

152

381

152

404

152

138

336

155

359

155

382

155

405

155

428

155

140

337

158

360

158

383

158

406

159

429

159

142

361

161

384

161

407

162

430

162

144

385

164

408

164

431

165

146

409

167

432

168

148

433

170

150

legend

Shaded boxes indicate flooded conditions.

Rated design values. The suction pressure will be lower than design value if outdoor air flow, entering

dry bulb, or entering wet bulb temperatures are lower than design.

noteS:
1. All pressures are listed psig and all temperatures in °F
2. Discharge temperatures GREATER than charted values indicate an UNDERCHARGED system.
3. Discharge temperatures LESS than charted values indicate an OVERCHARGED system.