beautypg.com

Warning – Reznor JS4BD (3ph) Unit Installation Manual User Manual

Page 5

background image

5

• Overcurrent protection must be provided at the branch

circuit distribution panel and sized as shown on the unit

rating label and according to applicable local codes.
See the unit rating plate for minimum circuit ampacity
and maximum overcurrent protection limits.

• Provide power supply for the unit in accordance with the

unit wiring diagram, and the unit rating plate. Connect
the line-voltage leads to the terminals on the contactor
inside the control compartment.

• Use only copper wire for the line voltage power supply

to this unit as listed in Table 1. Use proper code agency
listed conduit and a conduit connector for connecting
the supply wires to the unit. Use of rain tight conduit
is recommended.

• 208/230 Volt units are shipped from the factory wired

for 230 volt operation. For 208V operation, remove the
lead from the transformer terminal marked 240V and
connect it to the terminal marked 208V.

• Optional equipment requiring connection to the power

or control circuits must be wired in strict accordance
of the NEC (ANSI/NFPA 70), applicable local codes,
and the instructions provided with the equipment.

grounding

Warning:

the unit cabinet must have an uninterrupted or
unbroken electrical ground to minimize personal
injury if an electrical fault should occur. do not
use gas piping as an electrical ground

!

This unit must be electrically grounded in accordance
with local codes or, in the absence of local codes, with
the National Electrical Code (ANSI/NFPA 70) or the CSA
C22.1 Electrical Code. Use the grounding lug provided in
the control box for grounding the unit.

copper Wire SiZe — aWg

(1% Voltage drop)

Supply Wire length-Feet

Supply circuit

ampacity

200

150

100

50

6

8

10

14

15

4

6

8

12

20

4

6

8

10

25

4

4

6

10

30

3

4

6

8

35

3

4

6

8

40

2

3

4

6

45

2

3

4

6

50

2

3

4

6

55

1

2

3

4

60

Wire Size based on N.E.C. for 60° type copper conductors.

table 1. copper Wire Size

reverse rotation Verification
After making all of the power connections to the unit, the
rotation of the compressor must be checked. If the rotation
is in the wrong direction, the compressor will make an
abnormally loud noise. To check the rotation perform the
following steps:

1. Make sure the outside power disconnect is in the OFF

position.

2. Set the indoor thermostat to a set point that will call for

cooling.

3. Retun to the outside power disconnect and switch it

to the ON position. If the compressor is making an
abnormally loud noise, immediately switch the outside
power disconnect to the OFF position.

4. Switch any two of the three power leads at the power

connections to the unit.

5. SetReturn to the outside power disconnect and swith

it to the ON position.

6. Verify that the compressor is now running properly.

thermostat connections

Thermostat connections should be made in accordance
with the instructions supplied with the thermostat and
the indoor equipment.

The outdoor unit is designed to operate from a 24 VAC
Class II control circuit. The control circuit wiring must
comply with the current provisions of the NEC (ANSI/
NFPA 70) and with applicable local codes having
jurisdiction.

• The

low voltage wires must be properly connected to

the units low voltage terminal block. Recommended
wire gauge and wire lengths for typical thermostat
connections are listed in Table 2.

• The

thermostat should be mounted about 5 feet

above the floor on an inside wall. DO NOT install the
thermostat on an outside wall or any other location
where its operation may be adversely affected by radiant
heat from fireplaces, sunlight, or lighting fixtures, and
convective heat from warm air registers or electrical
appliances. Refer to the thermostat manufacturer’s
instruction sheet for detailed mounting and installation
information.

table 2. thermostat Wire gauge

thermostat

Wire gauge

recommended t-Stat Wire

unit to t-Stat (length in Ft)

2-Wire

(heating)

5-Wire

(heating/cooling)

24

55

25

22

90

45

20

140

70

18

225

110