beautypg.com

Caution, Installation instructions, Safety considerations (cont’d) – Reznor RDH Option - Installation - UV Light Installation - PreevA User Manual

Page 2: Location and components

background image

Page 2

CAUTION

Do not touch bulb glass without gloves.

Oil from fingerprints will permanently

etch glass of bulb and weaken structure.

Clean bulb after handling.

CAUTION

Bulb contains a small amount of

mercury. If a bulb breaks, clean with

care and dispose of using an envi-

ronmentally safe disposal method.

The Option UV2 light is factory-installed in the blower section, downstream of the

cooling coil. PREEVA Sizes 75-150 have one light fixture; Sizes 175-400 have

two. The bulb(s) are shipped in the blower section attached to each fixture but not

installed for use. When handling a bulb, wear gloves and DO NOT TOUCH the

glass; handle only on the ends.
In units with a DX coil, there will also be a parts bag containing three hole plugs.
Field-supplied components include a disconnect switch, 14 gauge wiring, metal

conduit or aluminum tape, and conduit connection or wire bushing.

Installation

Instructions

1. Turn off all power to the unit. Open the blower and electrical compartment

doors.

2. Ultra-violet light may damage certain plastics and exposed non-UVC protected

wires. Any field-supplied wiring or plastics in the blower compartment must be

wrapped with aluminum tape or installed in metal conduit.

Field

Connection

Panel

NOTE: The field connection panel is shown above with a unit on/off switch and a convenience outlet.

Both are optional and may not be on the unit being installed.

Mark and

drill hole(s)

for attaching

disconnect

switch.

Cooling Coil

Module

Blower

Section

Heat

Section

Electrical

Compartment

Airflow

FIGURE 1 -

Location and

Installation of

Field-Supplied

Disconnect Switch

Install disconnect switch wiring. Refer to the wiring diagram

in FIGURE 2. Wiring must be 14 gauge. Run wires from the

disconnect switch location through the factory-supplied con-

duit at the electrical compartment wall to the blower door

interlock switch junction box.

Example of one type of

field-installed UV light

disconnect switch

Factory-installed blower

door safety interlock switch

Safety Considerations (cont’d)

3. A separate, dedicated power

supply must be used for the

Option UV2 light. Do not use unit

wiring or control box connec-

tions.

Wiring must comply with national

and local codes. Power source

must be a suitable fused,

grounded, protected source with

the correct voltage. Voltages other than

115/1, 208/1, 230/1 will permanently

damage the lamp. Wire per

TABLE 1.

TABLE 1 - Supply Wiring

Wiring

Wire Color

Power

Black

Neutral

White

Ground

Green

4. Install the field-supplied disconnect switch. See FIGURE 1 and follow

instructions.
a) Locate the field connection panel. Mark and drill hole(s) for attaching field-

supplied disconnect switch .

Location and

Components