EXAMPLE: Supply voltage is 240-3-60.

AB = 243 v
BC = 236 v
AC = 238 v

Average Voltage = 243 + 236 + 238

3

= 239 v

Determine maximum deviation from average voltage:
(AB) 243 – 239 = 4 v
(BC) 239 – 236 = 3 v

(AC) 239 – 238 = 1 v
Maximum deviation is 4 v.

Determine percent voltage imbalance:
% Voltage Imbalance = 100 x

4

239

= 1.7%

This amount of phase imbalance is satisfactory as it is below

the maximum allowable 2%.

Table 3 — Electrical Data — 30MPA,MPW Units

LEGEND

*Supply Range — Units are suitable for use on electrical systems

where voltage supplied to the unit terminals is not below or above
the listed range limits.

NOTES:

1. All units have one field power terminal block.
2. Maximum incoming wire size is as follows:

For units with terminal block:
350 kcmil for unit sizes 030-045; 208/230-3-60 voltages.
2/0 for all other unit sizes; all voltages.
For units with optional non-fused disconnect:
350 kcmil for unit sizes:
030-045; 208/230-3-60 voltages.
045; 380-3-60 voltage.

3/0 for unit sizes:
015,020; 208/230-3-60 voltages.
020-040; 380-3-60 voltage.
030-045; 460-3-60 and 575-3-60 voltages.
2 AWG for unit sizes:
015; 380-3-60 voltage.
015-020; 460-3-60 and 575-3-60 voltages.

3. Additional control circuit power is not required.
4. Any field modification of factory wiring must be in compliance

with all applicable codes. Field-installed power wires must be
rated 75 C minimum.

5. Use copper conductors only.
6. Control circuit power supply is 24-v single phase. Control

power is supplied by the factory-installed control transformer.

IMPORTANT: If the supply voltage phase imbalance

is more than 2%, contact your local utility company

immediately.

UNIT SIZE

30MPA,MPW

VOLTS

NAMEPLATE

(3 ph, 60 Hz)

VOLTAGE*

COMPRESSOR

UNIT

Quantity

LRA
(ea.)

MCA

ICF

MOCP

Rec

Fuse

Min

Max

015

208/230

187

253

2

195

66.4

224.5

90

80

380

342

418

123

37.6

139.7

50

45

460

414

508

95

33.1

109.7

45

40

575

518

632

80

27.5

92.2

35

35

020

208/230

187

253

2

239

80.6

274.8

110

90

380

342

418

145

53.4

168.7

70

60

460

414

508

125

40.3

142.9

50

45

575

518

632

80

32.2

94.3

45

40

030

208/230

187

253

2

340

125.6

395.8

175

150

380

342

418

196

76.5

230.0

110

90

460

414

508

179

60.5

205.9

80

70

575

518

632

132

53.3

155.7

70

60

040

208/230

187

253

3

300

166.7

402.6

200

200

380

342

418

139

87.4

192.8

110

100

460

414

508

150

75.1

196.2

90

90

575

518

632

109

64.7

148.8

80

70

045

208/230

187

253

3

340

181.4

451.6

225

200

380

342

418

196

110.5

264.0

125

125

460

414

508

179

87.4

232.8

110

100

575

518

632

132

77.0

179.4

100

90

ICF

Maximum instantaneous current flow during starting.

kcmil

Thousand circular mils

LRA

Locked rotor amps.

MCA

Minimum circuit amps (for wire sizing). Complies with

NEC, Section 430-24.

MOCP

Maximum Overcurrent Protection

NEC

National Electrical Code (U.S.A.)

Rec
Fuse

Recommended dual element fuse amps (150% of com-

pressor RLA). Size up to the next standard fuse size.