beautypg.com

Cisco CRS-1 User Manual

Page 43

background image

3-3

Cisco CRS Carrier Routing System 8-Slot Line Card Chassis Site Planning Guide

OL-5802-09

Chapter 3 Technical and Environmental Specifications

Line Card Chassis Specifications

Table 3-2

lists the system specifications for the Cisco CRS 8-slot LCC with a modular configuration

power system installed.

Table 3-2

8-Slot Line Card Chassis Component and Power Specifications—Modular
Configuration Power

Description

Value

Supported Cards and Modules

8 modular services cards (MSCs) or forwarding
processor (FP) cards (line cards)

8 physical layer interface modules (PLIMs),

one for each MSC or FP

4 switch fabric cards (SFCs)

2 route processors (RP) cards or performance route
processor (PRP) cards

1 distributed route processor (DRP)

2 fan trays (with four fans per fan tray)

1 air filter

Power Shelves

2 AC or 2 DC power shelves

(cannot mix AC and DC power shelves in the chassis)

DC power shelf

Accepts up to 4 DC PMs

AC power shelf

Accepts up to 3 AC PMs

Maximum Power Consumption

(total input power)

Note

Proper grounding is also required at the site to
ensure that equipment is not damaged by
lightning or power surges.

Maximum DC

9.5 kW (assuming 88% efficiency)

Maximum AC

9.8 kW (assuming 92% efficiency)

Power Redundancy (2N)

DC

Up to four “A” battery plant feeds required for one
power shelf, and up to four “B” battery plant feeds
required for the other power shelf.

AC (Delta or Wye 3-phase)

Up to three “A” AC single-phase power sources and up
to three “B” AC single-phase power sources required.

DC Input

Nominal input voltage

–48 VDC North America

–60 VDC International

(range –40 to –72 VDC)

Input current

50 A max at –48 VDC

40 A max at –60 VDC

60 A at –40 VDC (low voltage extreme)