beautypg.com

Figure 2-10, Ac wye 3-phase wiring – Cisco CRS-1 User Manual

Page 34

background image

2-14

Cisco CRS Carrier Routing System 8-Slot Line Card Chassis Site Planning Guide

OL-5802-09

Chapter 2 Power and Cooling

AC Power Systems

Figure 2-10

AC Delta PDU Wiring

AC Wye 3-Phase Wiring

Figure 2-11

shows a PDU wired for AC Wye 3-phase power. As shown, input AC power is routed to

three internal 2.5-kW power modules in the rectifier, where it is converted into DC power (nominal
54.5 VDC, 46 ADC) and routed to the three load zones of the chassis.

The AC Wye PDU is shipped with a 14-foot (4.3-m) AC power cord. The power cord has a 5-pin IEC
60309 plug that is rated for 16 A (International) and 20 A (North America). It plugs into an IEC 60309
receptacle (16 or 20 A).

Figure 2-11

AC Wye PDU Wiring

2.5-kW

power

module

No. 2

2.5-kW

power

module

No. 3

122782

2.5-kW

power

module

No. 1

Phase X

Phase X

Phase Y

Phase Z

Safety Ground

Plugs into L15-30R receptacle

200 to 240 VAC, 30 A, 3-phase

122783

Phase X

Phase X

Phase Y

Phase Z

Neutral

Safety Ground

Plugs into IEC 60309 receptacle,
200 to 240 VAC (phase-to-neutral),
20 A (North America) 16 A (International), 3-phase

2.5-kW

power

module

No. 1

2.5-kW

power

module

No. 2

2.5-kW

power

module

No. 3