Cisco CRS Carrier Routing System 8-Slot Line Card Chassis Site Planning Guide
OL-5802-09
Chapter 2 Power and Cooling
Facility Cooling Requirements
Figure 2-19
Airflow Through the 8-Slot Line Card Chassis
The 8-slot LCC airflow volumes are as follows:
•
Chassis airflow: Up to 900 cubic feet (25,485 liters) per minute
•
Power system airflow: Up to 240 cubic feet (6800 liters) per minute
Facility Cooling Requirements
The 8-slot line card chassis dissipates considerable power that generates much heat. In large
configurations, additional air cooling is required to maintain correct operating temperatures. The room
air must be cooled by external cooling units that are installed as part of the routing system.
Heat dissipation and external cooling requirements for the 8-slot line card chassis are as follows:
•
Heat dissipation (fixed configuration): 28,720 BTUs per hour
•
Heat dissipation (modular configuration): 32,570 BTUs per hour
•
External cooling requirements: 2.3 tons
To ensure that the site provides the proper air circulation for the system:
•
Make certain that the site is as dust free as possible. Dusty environments can clog the air filter or
power supply intake vents, reducing the cooling airflow through the system.
•
Allow sufficient airflow by maintaining a minimum of 6 inches (15.2 cm) of clearance at both the
inlet and exhaust openings on the chassis and the fixed configuration power modules. If airflow is
blocked or restricted, or if inlet air is too warm, an over-temperature condition can occur. Under
extreme conditions, the environmental monitoring system shuts down the power to protect the
routing system components.
122784
Fan
Air enters
PLIM side
Power system
Fan
Air exits MSC and
fabric card side
Front
Rear
Air filter