beautypg.com

Microtel D51T v.1.0 User Manual

Page 29

background image

MICROTEL

D51T


27


Sensing voltage:

Open circuit sees 5 Volts (nominal)


Max. Loop Resistance:

10 killiohms


Max. Loop Capacitance:

100,000 picofarads


Isolation:

1500 Volts, transformer and optical isolation.


Fault Integration Delay:

00 – 99 seconds


AC Power Fail Detect:

Internal circuit, configurable enable and alarm delay


A.7 Temperature Measurement and Alarms

Type:

Onboard, internal to the enclosure, temperature IC

Accuracy:

+/- 5 degrees Fahrenheit

Reporting Resolution:

1 degree Fahrenheit

Low Temperature Alarm: Setpoint 00 to 99 degrees Farenheit
High Temperature Alarm: Setpoint 00 to 99 degrees Farenheit


A.8 Local Summary Alarm Contacts

Type:

Relay, Type 1A Contacts


Operation:

Normally energized (contacts closed),

De-energized (contacts open) when a Fault
condition is present; or, manual control of

output contacts via DTMF command.


Contact Rating:

10 VA, Resistive Load

Max. Switch Current:

0.5 Amp D.C


Max Switch Voltage:

48 Volts D.C.


Max. Carry Current:

1.25 Amps D.C.


Isolation:

1500 Volts