Sensing voltage:
Open circuit sees 5 Volts (nominal)
Max. Loop Resistance:
10 killiohms
Max. Loop Capacitance:
100,000 picofarads
Isolation:
1500 Volts, transformer and optical isolation.
Fault Integration Delay:
00 – 99 seconds
AC Power Fail Detect:
Internal circuit, configurable enable and alarm delay
A.7 Temperature Measurement and Alarms
Type:
Onboard, internal to the enclosure, temperature IC
Accuracy:
+/- 5 degrees Fahrenheit
Reporting Resolution:
1 degree Fahrenheit
Low Temperature Alarm: Setpoint 00 to 99 degrees Farenheit
High Temperature Alarm: Setpoint 00 to 99 degrees Farenheit
A.8 Local Summary Alarm Contacts
Type:
Relay, Type 1A Contacts
Operation:
Normally energized (contacts closed),
De-energized (contacts open) when a Fault
condition is present; or, manual control of
output contacts via DTMF command.
Contact Rating:
10 VA, Resistive Load
Max. Switch Current:
0.5 Amp D.C
Max Switch Voltage:
48 Volts D.C.
Max. Carry Current:
1.25 Amps D.C.
Isolation:
1500 Volts