4 current draw, 5 controller memory retention, 6 floor control relay contact rating – Keri Systems LC-508 Proximity Elevator Control User Manual
Page 3: Proximity elevator control panel
Proximity Elevator Control Panel
2305 Bering Drive
01941-001 Rev. B
San Jose, CA 95131 USA
(800) 260-5265 (408) 435-8400 FAX (408) 577-1792
Web: www.kerisys.com E-mail: [email protected]
Page 3 of 22
LC-502P/LC-508P
Quick S
tart Guide
3.4
Current Draw
•
500 mA maximum current draw for a Controller with all options installed (SB-500, LCD-1, and
Reader)
•
120 mA maximum for a LC-500P Controller
•
150 mA maximum for an SB-500 Satellite Board
•
refer to Table 1 on page 3 for Reader current draw
3.5
Controller Memory Retention
•
5 year lithium battery backup to support controller RAM and real-time clock
3.6
Floor Control Relay Contact Rating
•
24 VDC @ 1 Amp
When connecting to elevator control systems and the floor selection buttons, please
verify the elevator system voltages. Most elevator systems operate on DC or AC
voltages higher than the 24 VDC @ 1 Amp rating at which Keri Systems’ elevator
controllers are rated. Each installation should use isolation relays.
Keri Systems recommends establishing an interconnection point at which the access control system
and elevator control system connect, and to which both the access control company and the elevator
company have access. This assists in making the connections between the systems and in allowing
for independent system troubleshooting.
•
If the system voltages are different (or if you wish to fully protect the access control system
from transient voltage spikes), these connections should be made via isolation relays or relay
control boards.
•
If the system voltages are the same and both systems are fully protected, or if the system
connections are made between dry relay contacts, you may only need to use a terminal strip for
these connections.
Please consult your local building codes for proper installation requirements and check with local
permit departments to verify compliance. Elevator systems have Life Safety requirements and may
also require a connection to a fire control system.
Table 1: Current Draw by Reader Type
MS-3000
MS-4000
MS-5000
50 mA
50 mA
100 mA