5.4
Wiring Multiple Panels Together
As many as 24 floors may be controlled using a combination of LC-502Ps and LC-508Ps; the first
eight floors must be controlled by an LC-508P. After that, any combination of LC-502Ps and LC-
508Ps can be added to meet your floor requirements.
5.4.1
LC-508P/LC-502P Combination
Perform the following wiring instructions to accommodate an elevator application using an LC-
508P and one or more LC-502P panels (9 to 16 floors).
1. Make a complete set of connections to the LC-508P panel. Refer to Section 5.3 on page 15 and
Figure 10 on page 16 for all connections to the LC-508P.
2. Daisy-chain the Antenna and Ground reader connections from the LC-508P panel to the LC-
502P panel(s). Make the connections per the information in Table 5 and Figure 11 on page 18.
3. Daisy-chain the TxRx+, TxRx-, and Shield Network Communication connections from the
terminal strip on the LC-508P to each of the LC-502P panels. Make the connections per the
information in Table 6 and Figure 12 on page 19.
4. Refer to Section 5.2.1 on page 10 for the LC-502P floor relay connections.
5. Refer to Section 5.2.4 on page 15 for the LC-502P panel power connections.
Table 5: LC-508P to LC-502P
W-TB-B (Out)
W-TB-C (In)
LC-508P Reader Terminal Strip
LC-502P TB-5 or TB-6
Pin 2
Reader Antenna
Pin 1
Pin 1
Reader Ground
Pin 4
Table 6: LC-508P to LC-502P Panel Network
Communication Wiring
W-TB-B (Out)
W-TB-C (In)
Connection
LC-502P TB-1
Pin 4
TxRx-
Pin 1
Pin 5
TxRx+
Pin 2
Pin 6
Shield
Pin 3