5.4.2

LC-508P/LC-508P Combination

Perform the following wiring instructions to accommodate an elevator application using two LC-
508P panels; up to 16 floors (for 24 floors, add a third LC-508P and continue the daisy-chain wiring
to the third panel).

1. Make a complete set of connections to the first LC-508P panel. Refer to Section 5.3 on page 15

for all connections to the LC-508P. This panel must have the master elevator controller (the
controller with address 1).

2. Daisy-chain the Antenna and Ground reader connections from the terminal strip on the first

panel to the terminal strip on the second panel. Make the connections per the information in
Table 7 and Figure 13.

Figure 13: LC-508P to LC-508P Wiring Connections

Table 7: LC-508P to LC-508P

First LC-508P Reader

Terminal Strip

Second LC-508P Reader

Terminal Strip

Reader Antenna

Reader Antenna

Reader Ground

Reader Ground