Carrier 58GFA User Manual

Page 3

background image

b. Remove blower access door after removing 2 screws.

c. Reach up behind top plate, tilt filters toward center of

return-air plenum, remove filters, and replace or clean as
needed.

d. Furnaces are equipped with permanent, washable filters.

Clean filters with tap water. Spray water through filter in
opposite direction of airflow.

e. Rinse and let dry. Oiling or coating of filters is not

recommended or required.

f. Reinstall filters.

g. Replace access door and secure with 2 screws.

h. Restore electrical power to furnace.

2. Upflow

Each furnace requires 1 or 2 filters which are installed in the
blower compartment. (See Fig. 4.)

To remove filters for cleaning or replacement, proceed as
follows:

a. Disconnect electrical power before removing access doors.

b. Remove blower and control access doors.

c. Release filter retainer from clip at front of furnace casing.

(See Fig. 4.) For side return, clips may be used on either or
both sides of the furnace.

d. Slide filter out.

e. Furnaces are equipped with permanent, washable filters.

Clean filter with tap water. Spray water through filter in
opposite direction of airflow.

f. Rinse and let dry. Oiling or coating of filter is not

recommended or required.

g. Reinstall filter.

h. Replace access doors.

i. Restore electrical power to furnace.

BLOWER MOTOR AND WHEEL — For long life, economy, and
high efficiency, clean accumulated dirt and grease from the blower
wheel and motor annually.

The following steps should be performed by a qualified service
technician:

Some motors have prelubricated sealed bearings and require no
lubrication. These motors can be identified by the absence of oil
ports on each end of the motor. For motors with oil ports, lubricate
motor every 5 years if motor is used on intermittent operation
(thermostat FAN switch in AUTO position), or every 2 years if
motor is in continuous operation (thermostat FAN switch in ON
position).

Remember to disconnect the electrical supply before removing
access doors.

Clean and lubricate as follows:

1. Remove 2 screws from blower access door (downflow furnace

only). Remove blower access door.

2. Remove vent pipe enclosure (downflow furnace only) and

disconnect short piece of vent pipe from relief box.

3. Disconnect wires from auxiliary limit on blower housing

(downflow furnace only).

4. Remove control box.

5. Remove electrical leads from numbered side of blower speed

selector. (See Fig. 4 and 5.) Note location of wires for
reassembly.

6. Remove screws holding blower assembly to blower deck and

slide blower assembly out of furnace.

7. Squeeze side tabs of blower speed selector and pull it out of

blower housing.

8. Loosen screw in strap holding motor capacitor to blower

housing and slide capacitor out from under strap.

Fig. 4—Model 58GFA Upflow

A92178

DRAFT
SAFEGUARD
SWITCH

RELIEF

BOX

MOUNTING

SCREWS

FLUE
COLLECTOR
BOX

GAS
VALVE

PILOT

SPEED
SELECTOR

FILTER
RETAINER

WASHABLE
FILTER

CONTROL

BOX

Fig. 5—Model 58DFA Downflow

A92179

VENT PIPE
ENCLOSURE

CONTROL
BOX

DRAFT
SAFEGUARD
SWITCH

FLUE
COLLECTOR
BOX

AUXILIARY
LIMIT SWITCH
(NOT VISIBLE)

SPEED

SELECTOR

MOUNTING

SCREWS

RELIEF

BOX

3